Installation of Final Filters:

Precision Pak bag

filter

PrecisionCell,

Superflow V, or

Rigid-Air filter with

a

Single Header

Drawing Notes

1.Framing members of extruded aluminum are factory-cut to exact length, pre-drilled and gasketed.

2.One vertical support for the center of the upstream side will be furnished on modules nominal 8 ft. wide. Wider mod- ules will be furnished with vertical supports on both the upstream and downstre m sides.

3.Sealing levers are located at the end of each horizontal row on the left when f cing the module on

the upstream side unless specified on the right or on the downstream side.

4. The largest single module is 12 ft. high by 14 ft. wide. Modules may be combined to form larger banks.

Installation of Final Filters:

1.Install gasketed filters with pleats vertical wherever possible.

2.Place sealing lever in locked position and hold filter on the downstream side of the module.

3.Insert the top of the filter into the upper narrow track until it clears the lower flange.

4.Drop the filter into the bottom narrow track. Fill the row with filters, moving them to the side opposite the sealing lever.

5.Unlock the lever to seal the row airtight.

 

 

Guide Specifications

 

1.0 Framing Modules

2.4 The prefilter track shall be separate to allow

1.1 Filter framing modules shall be K-Trac as manu-

removal and insertion of prefilters without disturb-

ing the final filters.

 

factured by Flanders.

 

 

 

2.0 Construction

 

2.5 Each horizontal row of prefilters and final filters

 

shall include factory-installed positive-sealing

2.1 Extruded alum num framing members shall be

bars to permit easy changeout of filters. Gasket

on filters must be compressed during operation.

 

Type 6063-T5, w th an average thickness of .095”

 

 

 

They shall be cut to size and drilled for simple

2.6 Modules shall be complete with speed-screws

speed screw assembly into modules of the sizes

necessary for field assembly.

 

noted in the schedules and plans.

 

 

2.2 Both pr filt

r and final filter tracks shall be perma-

3.0 Features

 

 

 

n

ntly gask

t d to eliminate air bypass.

3.1 Model number and capacities shall be as specified

2.3 W

ere required, vertical support members shall be

and/or shown on the drawings.

 

 

 

furnis ed to support horizontal members.

3.2 Provide options as specified.

 

 

 

 

 

 

 