Honeywell 11255 manual Installation Considerations, Performance Data, 75% XDH

Models: 11255

1 136
Download 136 pages 57.63 Kb
Page 73
Image 73
75% XDH

Installation Considerations

Precision Pak bag filters may be installed in Flanders Type 9 Holding Frames, K-Trac Filter Framing Modules, Sureseal Side Access Housing or in simi- lar existing hardware.

Type 9 Holding Frames are riveted together to form a bank and may be installed for upstream or down- stream service. K-Trac Filter Framing Modules are especially suitable for medium to large built-up filter banks. Smaller systems and systems with minimum upstream access space are best served using Sureseal Side Access Housings.

Grams of dust held

600

500

400

300

200

100

0

XDH

F i b e r Synthetic

Glass

Comparison of XDH o fiberglass and synthetic filters with the same media content.

Performance Data

 

 

 

75% XDH

Synthetic Media Filters

 

 

 

 

Nominal

Number

Nom.

Nom

Media

375 fpm

 

500 fpm

625 fpm

Depth

of

Width

Height

Area

 

 

 

 

 

 

 

cfm

PD

 

cfm

PD

cfm

PD

(inch)

Pockets

(inch)

(inch)

(sq. ft)

 

12

 

12

24

24

52

1500

0.25

 

2000

0.34

2000

0.56

12

 

6

12

24

26

750

0.25

 

1000

0.34

1250

0.56

22

 

6

24

24

48

1500

0.23

 

2000

0.32

2000

0.44

22

 

3

12

24

24

750

0.23

 

1000

0.32

1250

0.44

22

 

8

24

24

64

1500

0.20

 

2000

0.28

2000

0.38

22

 

4

12

24

32

750

0.20

 

1000

0.28

1250

0.38

22

 

10

24

24

79

1500

0.19

 

2000

0.26

2000

0.36

22

 

5

12

24

40

750

0.19

 

1000

0.26

1250

0.36

26

 

6

24

24

56

1500

0.22

 

2000

0.31

2000

0.42

26

 

3

12

24

28

750

0.22

 

1000

0.31

1250

0.42

26

 

8

24

24

75

1500

0.19

 

2000

0.27

2000

0.37

26

 

4

12

24

38

750

0.19

 

1000

0.27

1250

0.37

26

 

10

24

24

94

1500

0.16

 

2000

0.24

2000

0.34

26

 

5

12

24

47

750

0.16

 

1000

0.24

1250

0.34

30

 

6

24

24

65

1500

0.21

 

2000

0.30

2000

0.40

30

 

3

12

24

33

750

0.21

 

1000

0.30

1250

0.40

30

 

8

24

24

87

1500

0.17

 

2000

0.26

2000

0.36

30

 

4

12

24

43

750

0.17

 

1000

0.26

1250

0.36

30

 

10

24

24

108

1500

0.13

 

2000

0.22

2000

0.32

30

 

5

12

24

54

750

0.13

 

1000

0.22

1250

0.32

1.PD represents clean pressure drop in inches w.g.

2.The recommended final pressure drop for all models is 1.0 inch w.g.

3.Filt rs in all standard depths may be operated down to zero air flow on VAV systems.

4.Gross m dia area is approximately 7% more than the net media area listed.

5.Performance values stated may be averages typical of the products listed. Contact factory for actual per- formance test reports on specific products.

Flanders - Foremost in Air Filtration