Honeywell 11255 manual The Pre Pleat Series of Pleated Air filters, Guide Specifications, General

Models: 11255

1 136
Download 136 pages 57.63 Kb
Page 35
Image 35
The Pre Pleat Series of Pleated Air filters

The Pre Pleat Series of Pleated Air filters

Pre Pleat Class 1 air filters are designed for applications where a UL Class 1 fire rated filter is required and metal frames are unsuitable.

Pre Pleat HT air filters are designed for applications where the temperatures reach up to 400ºF.

62R high efficiency pleated air filters contain an electrostatically charged filtration media which has a higher dust holding capac- ity.

 

Pre Pleat HV air filters are

 

designed to operate in

 

high velocity and turbulent

 

air applications where

 

standard pleated filters

 

tend to fail.

 

Guide Specifications

1.0 General

upstream and downstream sides, and shall have

1.1 Medium efficiency fil ers shall be Pre Pleat 40

locking corners.

 

extended surface p ea ed fil ers as manufactured

3.0 Performance

by Flanders..

3.1 Initial and final resistances shall not exceed the

1.2 Filter sizes and capac t es shall be as scheduled

scheduled values.

on the drawings.

3.2 Media area must equal or exceed that of the spec-

1.3 Filters shall be UL 900 Class 1 or 2 listed.

ified filter.

 

2.0 Filt r Construction

3.3 The average atmospheric dust spot efficiency

2.1 Filt rs shall be constructed of reinforced, non-

shall be 25-30% as determined by ASHRAE

Standard 52.1 test methods.

wov n cotton/synthetic blend media laminated to

 

an expanded metal grid on the air leaving side

3.4 The manufacturer shall guarantee performance as

and formed into v-configuration pleats.

stated in the literature within tolerances as out-

2.2 Frame shall be moisture-resistant board with diag-

lined in Section 7.4 of ARI Standard 850.

 

onal and horizontal support members on the

35

Page 35
Image 35