Honeywell 11255 Superflow 2K Performance, Superflow 2K Selection, Guide Specifications, General

Models: 11255

1 136
Download 136 pages 57.63 Kb
Page 94
Image 94
Superflow 2K Performance

Superflow 2K Performance

The Superflow 2K filters offer HEPA efficiency at an ultra low pressure drop for HVAC systems supplying air to critical areas.

Figure 1 illustrates the Superflow 2K pressure drop as a function of air flow rate for gasket seal and gel seal designs.

Superflow 2K Selection

All products have a rated overall efficiency of 99.99% at 0.30 µm and a maximum pressure drop of

1.0 inch w.g. at the rated flow. Specify the following:

Material Types:

8

= Galvanized

 

 

5

= Aluminum

 

 

3

= Stainless Steel

Gasket Types:

G = Neoprene

F = Blu Jel

Gasket Locations:

1

= Upstream

2 = Downstream

Model Number

SF2K-(*)-G(location)-GG

SF2K-(*)-G(location)-CG

SF2K-(*)-G(location)-YY

SF2K-(*)-G(location)-UY

SF2K-(*)-F(location)-GG

SF2K-(*)-F(location)-CG

SF2K-(*)-F(location)-YY

SF2K-(*)-F(location)-UY

Nominal Size

24" x 24" x 12" 12" x 24" x 12" 24" x 24" x 12" 12" x 24" x 12" 24" x 24" x 12" 12" x 24" x 12" 24" x 24" x 12" 12" x 24" x 12"

Actual Size

24" x 24" x 11-1/2" 12" x 24" x 11-1/2"

23-3/8" x 23-3/8" x 11-1/2" 11-3/8" x 23-3/8" x 11-1/2"

24" x 24" x 11-1/2" 12" x 24" x 11-1/2"

23-3/8" x 23-3/8" x 11-1/2" 11-3/8" x 23-3/8" x 11-1/2"

Media Area

290 sq. ft.

140 sq. ft.

280 sq. ft.

135 sq. ft.

270 sq. ft.

130 sq. ft.

260 sq. ft.

125 sq. ft.

Rated Flow

2000 cfm

900cfm 1900 cfm

855cfm 1760 cfm

790cfm 1670 cfm

750cfm

*Insert Material Type

Guide Specifications

1.0

General

 

2.2The filter frame shall be 20 ga. galvaneal steel and

1.1

HEPA filters sha

be F anders Superflow 2K as

shall consist of eight C-channel supports

attached without the use of mechanical fasten-

 

manufactured by F anders.

 

ers. The media packs shall be sealed around the

1.2

Filter sizes, e c enc es and capacities shall be

entire periphery to the frame with a two compo-

 

as specified on the drawings.

 

nent polyurethane.

 

 

 

2.0

Construction

3.0

Performance

 

 

2.1

Filt rs shall be constructed with ten 1” pleated

3.1

The minimum filter efficiency shall be 99.99% at

 

m dia packs arranged in a V-bank configuration.

 

 

0.30 µm when tested with polydisperse DOP

 

The m dia packs shall be formed by pleating wet

 

 

 

aerosol at the rated air flow.

 

laid micro-fiberglass media with continuous

 

 

3.2

The maximum pressure drop shall be 1.0” w.g. at

 

beads of a nonvolatile adhesive spaced 1-1/4”

 

 

 

apart.

the rated air flow.

 

94

Page 94
Image 94
Honeywell 11255 manual Superflow 2K Performance, Superflow 2K Selection, Guide Specifications, General, Construction