Application Guidelines

PrecisionCell filters may be used wherever job requirements dictate totally rigid filters and available space will allow only minimal inline depth.

PrecisionCell filters should be selected using 24” x 24” and 24” x 12” face sizes. This allows for 12” increments in height and width of the filter bank and insures that replacement cartridges will be readily available.

PrecisionCell filters should be installed with separa- tors vertical where ever possible. It is permissible to install 24” x 12” face size cartridges with separators horizontal if necessary to meet the size require- ments of the filter bank.

Prefilters

We recommend that Prepleat 40 pleated panel fil- ters or Precision Pak bag filters be used as prefilters for PrecisionCell installations. Where there must be long intervals between filter changes, we recom- mend using 65% ASHRAE rated PrecisionPak as prefilters. Refer to individual bulletins for perform- ance data on these prefilters.

VAV Systems

Filter banks should be sized so that the maximum rated flow at design conditions falls within the pub- lished recommended velocities. PrecisionCell filters may be applied at any capacity between ze o flow and cataloged capacities.

Hospital Applications

PrecisionCell filters are the preferred selection for hospital systems where code or good practice require that the filters be down tream of coils.

Gasketed Headers

PrecisionCell headered filters installed in Flanders K-Trac Filter Framing Modules or Sureseal Side Access Housings require gaskets on opposite head- er sides to prevent ir bypass.

To specify filters with g sketed headers, add suffix “S” to “H” to the model number as follows:

Model Number - S: Gaskets are on the sides paral- lel to t e separators.

Model Number - H: Gaskets are on the sides per- pendicular to the separators.

 

Guide Specifications

1.0 General

 

2.3 The enclosing frame shall be assembled in a

1.1 Medium and high efficiency igid filte s shall be

rigid manner and shall incorporate a single or

double header as required by job conditions.

PrecisionCell extended media sepa ator type

 

rigid filters as manufactured by Flande s.

2.4 Filters shall be UL 900 Class 1 listed.

1.2 Filter sizes, efficienci s and capacities shall be

3.0 Performance

as scheduled on

he drawings.

3.1 Initial and final resistances shall not exceed the

 

 

2.0 Filter Construction

 

scheduled values.

2.1 Filters sha

be constructed by pleating a

3.2 Media area must equal or exceed that of the

continuous sheet of moisture-resistant water-

specified filter.

laid micro- ine glass media into closely spaced

3.3 The average efficiency shall be as determined

pleats with hemmed-edge corrugated aluminum

by the ASHRAE Standard 52.1 test methods.

separators.

 

 

3.4 The manufacturer shall guarantee performance

2.2 The filt r pack shall be sealed into a 24 ga. steel

as stated in the literature within tolerances as

frame.

 

 

outlined in Section 7.4 of ARI Standard 850.

 

 

 

 

 