Performance Data Notes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal Size

250 FPM

375 FPM

500

FPM

625 FPM

750 FPM

Media

Wt.

 

Efficiency

Model

HxWxD

 

 

 

 

 

 

 

 

 

 

Area

Each

%

Number

Inches

CFM

PD

CFM

PD

CFM

PD

CFM

PD

CFM

PD

(Sq.Ft)

(Lbs.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

95% DOP

SFVD-95A12

24 x 24 x 12

1000

0.28

1500

0.55

2000

0.75

2500

0.80

*

*

196

18

 

95% DOP

SFVD-95B12

20 x 24 x 12

800

0.28

1200

0.55

1600

0.75

2000

0.80

*

*

162

14

 

95% DOP

SFVD-95C12

12 x 24 x 12

500

0.28

750

0.55

1000

0.75

1250

0.80

*

*

98

9

 

98%

SFV-98A12

24 x 24 x 12

1000

0.25

1500

0.45

2000

0.60

2500

1.0

*

*

196

17

 

98%

SFV-98B12

20 x 24 x 12

800

0.25

1200

0.45

1600

0.60

2000

1.0

*

*

162

13

 

98%

SFV-98C12

12 x 24 x 12

500

0.25

750

0.45

1000

0.60

1250

1.0

*

*

98

8

95%

SFV-95A12

24 x 24 x 12

1000

0.14

1500

0.27

2000

0.36

2500

0.51

3000

0.64

196

17

95%

SFV-95B12

20 x 24 x 12

800

0.14

1200

0.27

1600

0.36

2000

0.51

2400

0.64

162

13

95%

SFV-95C12

12 x 24 x 12

500

0.14

750

0.27

1000

0.36

1250

0.51

1500

0.64

98

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85%

SFV-85A12

24 x 24 x 12

1000

0.07

1500

0.18

2000

0.27

2500

0.40

3000

0.6

196

17

 

85%

SFV-85B12

20 x 24 x 12

800

0.07

1200

0.18

1600

0.27

2000

0.40

2400

0.6

162

13

 

85%

SFV-85C12

12 x 24 x 12

500

0.07

750

0.18

1000

0.27

1250

0.40

1500

0.6

98

8

 

65%

SFV-65A12

24 x 24 x 12

1000

0.05

1500

0.15

2000

0.25

2500

0.38

3000

0.52

196

17

65%

SFV-65B12

20 x 24 x 12

800

0.05

1200

0.15

1600

0.25

2000

0.38

2400

0.52

162

13

65%

SFV-65C12

12 x 24 x12

500

0.05

750

0.15

1000

0.25

1250

0.38

1500

0.52

98

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Performance Data Notes:

1.PD represents clean pressure drop in inches w.g. The recommended final pressure drop for all models is 2.0 inch w.g. Maximum final pressure drop is 3.2 inch w.g.

2.Operation down to zero air flow is satisfactory for all models

3.Efficiency is average and is based on ASHRAE Standard 52.1 test methods for 65, 85, 95 and 98% filters. Performance values stated may be averages typical of the products listed. Contact factory for actual performance test reports on specific products.

4.Performance tolerances conform to section 7.4 of ARI Standard 850.

5.Actual filter header is 5/16 inch under on height an width. Actual depth is 11-1/2 inch

Installation Consider tions

Superflow-V filters m y be installed in Flanders Type 9

Holding Frames, K-Trac Filter Framing Modules, Sureseal Side Access Housings or in similar existing hardware. Type 9 Holding Frames are riveted toget er to form a filter bank. K-Track Filter Framing Modules are especially suitable for medium to large built-up filter banks. Smaller systems and systems with minimum upstream access space are best served using Sureseal Side Access Housings.

Gasketed Headers are Standard

Superflow-V filters are furnished with a peripheral head- er on the air entering side and with foam gaskets on the “H” dimension for the 24 x 24 model and “W” dimension on the 12 x 24 and 20 x 24 models.

Guide Specifications

1.0 General

3.0 Performance

1.1 Medium and high efficiency ex ended surface low

3.1 Initial and final resistances shall not exceed the

pressure drop m n p eat f ters shall be Superflow-

scheduled values.

V models as manu actured by Flanders.

3.2 Media area must equal or exceed that of the spec-

 

1.2 Filter sizes, e iciencies and capacities shall be as

ified filter.

scheduled on the drawings.

3.3 The average efficiency shall be as determined by

 

2.0 Filter Construction

ASHRAE Standard 52.1 test methods.

3.4 Filters shall be UL 900 Class 2 listed.

2.1 Filt rs shall consist of multiple minipleat panels

 

bond d to flame-retardant plastic panels on top

 

and bottom and encased in a corrosion-resistant

 

steel frame.

 