Diagnostics and Troubleshooting - User Interface

 

 

Table 26 - LED Indications on Ethernet Hub

 

 

 

 

 

 

LED

LED State/Color

Indicates Condition:

 

 

 

 

 

 

 

10Base-T port

 

 

 

 

(I/O Expansion –C50

 

 

 

 

CPU only)

 

 

 

 

XMT (upper LED)

Green (On/Off)

On while a message is being sent from the Main

 

 

 

 

CPU; otherwise Off.

 

 

LINK (lower LED)

Green (On/Off)

On while the Main CPU is receiving a message.

 

 

 

 

Remains On as long as host is present; Off

 

 

 

 

when the host is removed from the link.

 

 

 

 

 

 

 

 

NOTE: These LEDs indicate activity on the communication port, they are

 

 

 

controlled by hardware (PHY chip), not by software.

 

 

 

 

 

 

User Interface

Table 27 lists Controller Module diagnostic indications (Operator Interface messages, and Status LED) along with causes of the indications, automatic control file actions, and suggested user actions.

Hazardous voltages exist in the equipment enclosure.

Identify and avoid contact with voltage sources.

Disconnect power before servicing. (More than one switch may be required to disconnect all power.)

Failure to comply with these instructions could result in death or serious injury.

Table 27 - Controller Module Diagnostics

Table 27 - Controller Module Diagnostics

OI Screen

OI Screen

Number of

Possible Cause

Control File Action

User Action

Item

Item Value

LED

 

 

 

 

 

 

Strobes

 

 

 

 

N/A

N/A

1

RAM failed on power-

Executes an infinite loop

1.

Cycle power

 

 

 

up.

that toggles the LED.

2.

Replace CPU

 

 

 

 

Communications and

 

 

 

 

3.

Replace rack

 

 

 

 

control are disabled.

N/A

N/A

1

ROM failed on power-

Executes an infinite loop

1.

Cycle power

 

 

 

up.

that toggles the LED.

2.

Replace CPU

 

 

 

 

Communications and

 

 

 

 

3.

Replace rack

 

 

 

 

control are disabled.

 

 

 

 

 

 

SYSTEM

GOOD

N/A

N/A

N/A

N/A

 

FORCED

2

A block has an output

None

Remove force on

 

OUTPUT

 

that is forced.

 

block output.

 

 

 

 

 

 

 

Revision 5

HC900 Hybrid Controller Installation and User Guide

121

9/03

 

 

Page 131
Image 131