| Specifications - Analog Output Modules | |
| Analog Output Modules | ||
|
|
|
|
| Feature | Description |
|
|
|
|
|
| Number of outputs | 4 isolated outputs per module |
|
|
|
|
|
| Isolation | 500 Vdc |
|
|
| 600 Vdc from logic |
|
|
|
|
|
| Output device | MOSFET |
|
|
|
|
|
| Load resistance | 0 to 750 ohms |
|
|
|
|
|
| Accuracy | 0.1% of full scale at reference conditions |
|
|
|
|
|
| D/A Resolution | 12 bits |
|
|
|
|
|
| Output Current | 0 to 21.8mA into 0 to 750 Ohms, range selectable |
|
|
|
|
|
| Minimum current sensing | > 3.5 mA per output |
|
|
|
|
|
| Calibration Data | Data is stored in |
|
|
| Redundant Factory Calibration, with automatic rejection of Bad version |
|
|
| Individual Channel Field Calibration |
|
|
|
|
|
| Failsafe Outputs | Timeout causes outputs to be forced to configured values. |
|
|
|
|
|
| Diagnostics | Monitoring of Factory Calibration, Field Calibration, Configuration, and +24 Vdc |
|
|
| power supply. |
|
|
|
|
|
| Output Verification | Feedback to CPU that indicates output current flowing. |
|
|
|
|
|
Revision 5 | HC900 Hybrid Controller Installation and User Guide | 163 |
9/03 |
|
|