Specifications - DC Output Module

 

DC Output Module

 

 

 

 

 

 

 

Feature

Description

 

 

 

 

 

 

Outputs

16 (current sinking, low side)

 

 

 

 

 

 

Isolation

2 groups of 8 outputs/group

 

 

 

 

 

 

Operating Voltage

6.5 to 32 Vdc (5.0 to 6.5 V @ < 0.5 A per channel)

 

 

 

 

 

 

Output type

Intelligent Power Switch (IPS)

 

 

 

 

 

 

Peak Voltage

34Vdc

 

 

 

 

 

 

On-State Voltage drop

0.3 Vdc @ 1 A load

 

 

 

 

 

 

Overload Protection

Electronic high-current and high temperature limiting, resets after cycling field

 

 

 

power

 

 

 

 

 

 

Maximum Load Current

1 A per point, 8 A max. per card, resistive load

 

 

 

 

 

 

Maximum Leakage Current

0.15 mA @ 32 Vdc

 

 

 

 

 

 

Maximum In-rush Current

4 A for 10 ms

 

 

 

 

 

 

Minimum Load

0.0 mA

 

 

 

 

 

 

Base Power Required

426 mA @ 5 V

 

 

 

 

 

 

Response Time

Off to On: 10 ms

 

 

 

On to Off: 5 ms

 

 

 

 

 

 

Fuses

Electronic limiting

 

 

 

 

 

Revision 5