I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams
AC Output Module Wiring
The AC Output Module provides eight output circuits. Each output is isolated from the other outputs. An example of AC output wiring is shown in Figure 45. Specifications for this module and for other modules are given in the Specifications section of this manual.
Output Loading
Voltage: 85 to 240 Vac
Maximum per output: 2.0A resistive load
Maximum per module: 8.0A
NOTE
When exceeding 1.0 A per output, it is recommended (but not required) to connect the
Jumper Comb
A
Replaceable Fuses
Each output circuit on the AC Output Module includes a
Replacement fuse is from Wickmann, part #3741315041. This is a 3.15 Amp time lag fuse with UL/CSA approval for 250 VAC.
Hazardous voltages exist at terminal blocks.
•Using switches at field devices, disconnect the field wiring from power sources before servicing.
Failure to comply with these instructions could result in death or serious injury.
80 | HC900 Hybrid Controller Installation and User Guide | Revision 5 |
|
| 9/03 |