Honeywell HC900 manual AC Output Module Wiring, Output Loading, Replaceable Fuses

Models: HC900

1 228
Download 228 pages 17.95 Kb
Page 90
Image 90

I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams

AC Output Module Wiring

The AC Output Module provides eight output circuits. Each output is isolated from the other outputs. An example of AC output wiring is shown in Figure 45. Specifications for this module and for other modules are given in the Specifications section of this manual.

Output Loading

Voltage: 85 to 240 Vac

Maximum per output: 2.0A resistive load

Maximum per module: 8.0A

NOTE

When exceeding 1.0 A per output, it is recommended (but not required) to connect the high-current loads to every other output - for example, outputs 1, 3, 5, 7 or 2, 4, 6, 8. This distributes heat more evenly across the heat sink.

Jumper Comb

A ten-position jumper comb is available for inter-connecting all L1 (Hot) terminals (1, 3, 5, 7, 9, 11, 13, 15, 17, 19). See Figure 46.

Replaceable Fuses

Each output circuit on the AC Output Module includes a (plug-in) replaceable fuse.

Replacement fuse is from Wickmann, part #3741315041. This is a 3.15 Amp time lag fuse with UL/CSA approval for 250 VAC.

Hazardous voltages exist at terminal blocks.

Using switches at field devices, disconnect the field wiring from power sources before servicing.

Failure to comply with these instructions could result in death or serious injury.

80

HC900 Hybrid Controller Installation and User Guide

Revision 5

 

 

9/03

Page 90
Image 90
Honeywell HC900 manual AC Output Module Wiring, Output Loading, Replaceable Fuses