Communications Installation - Connecting the HC900 Controller to a PC with the Hybrid Control Designer Software
SixNet VT-MODEM Industrial External Modem
Step | Action |
1Connect the modem to a PC. If your PC’s
2Connect power to the modem. You will need to supply an external power supply with a DC voltage between 10 and 30 VDC.
3
4Run a serial communication port program such as Hyperterminal.
5Within the communication program, select the port to which the modem is connected.
6Configure the port to these settings:
baud rate = 9600, 19200, 38400, 57600 (must match baud rate configured in HC900 controller
data bits = 8 parity = none stop bits = 1
flow control = none
7In the program's terminal window, restore factory defaults by
AT &F0
Then, press the ENTER key.
8In the program’s terminal window,
AT E1 Q0
Then, press the ENTER key. The modem should give an OK response.
9
AT &Y0 &C0 &D0 &R1 &S0 &K0 S0=1
The Modem should respond with OK.
10
AT E0 Q1 &W0
The Modem will not respond.
11Power down the modem and disconnect it from the PC.
12Connect the modem to the
13Connect the modem to a telephone jack.
14
15On a remote computer, run Hybrid Control Designer software.
16Set up the PC software to dial the HC900 Controller.
17Use the PC software
Revision 5 | HC900 Hybrid Controller Installation and User Guide | 99 |