Appendix B Installation of Remote Termination Panels (RTPs) - Digital Input/Digital Output/Analog Output

Digital Input/Digital Output/Analog Output

 

The DI/DO/AO-RTP is for use with the following modules:

See page

 

4-point Analog Output

194

 

16-point Contact Digital Input

195

 

16-point DC Digital Input

197

 

16-point AC Digital Input

198

 

16-point DC Digital Output

200

 

8-point AC Digital Output

201

 

 

 

 

 

 

4 Point Analog Output

 

Step

 

Action

 

 

 

 

 

 

 

1

ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.

 

Mount RTP cable assembly to HC900 Controller (Figure 60).

 

 

Remove appropriate key tabs from terminal block to allow mating with the module. See page 64.

 

 

Connect desired cable to AO module at controller. Choose from:

 

 

900RTC-L010 Remote Terminal Low Voltage Cable Assembly, 1.0 meters long

 

 

900RTC-L025 Remote Terminal Low Voltage Cable Assembly, 2.5 meters long.

 

 

900RTC-L050 Remote Terminal Low Voltage Cable Assembly, 5.0 meters long

 

 

Install AO module label onto the module connector cover.

 

 

Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring

 

 

shields must be grounded as described in the shield grounding section (page 60).

 

 

 

 

 

 

2

Mount RTP to DIN rail.

 

 

 

Latch to rail. See page 205.

 

 

 

Connect cable to RTP

 

 

 

3

Set/verify jumper positions as shown for use with an analog output module.

 

 

 

 

 

 

Jumper open

 

 

 

 

 

 

 

 

 

 

 

 

Jumper closed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW1 is not used. Module RIUP is not affected by using the RTP.

 

See page 203 for RTP internal schematic.

 

 

 

 

 

 

 

 

194

HC900 Hybrid Controller Installation and User Guide

Revision 5

 

 

9/03