Appendix B Installation of Remote Termination Panels (RTPs) - Digital Input/Digital Output/Analog Output
Digital Input/Digital Output/Analog Output
| The | See page | ||||
| • | 194 | ||||
| • | 195 | ||||
| • | 197 | ||||
| • | 198 | ||||
| • | 200 | ||||
| • | 201 | ||||
|
|
|
|
|
| |
4 Point Analog Output |
| |||||
Step |
| Action |
| |||
|
|
|
|
|
| |
1 | ATTENTION: RTP and cables are intended for permanent installation within their own enclosure. | |||||
| Mount RTP cable assembly to HC900 Controller (Figure 60). | |||||
|
| • Remove appropriate key tabs from terminal block to allow mating with the module. See page 64. | ||||
|
| • Connect desired cable to AO module at controller. Choose from: | ||||
|
| |||||
|
| |||||
|
| |||||
|
| • Install AO module label onto the module connector cover. | ||||
|
| • Connect shield drain wire to the grounding bars at the base of the HC900 rack. All | ||||
|
| shields must be grounded as described in the shield grounding section (page 60). | ||||
|
|
|
|
|
| |
2 | Mount RTP to DIN rail. |
| ||||
|
| • Latch to rail. See page 205. |
| |||
|
| • Connect cable to RTP |
| |||
|
| |||||
3 | Set/verify jumper positions as shown for use with an analog output module. | |||||
|
|
|
|
|
| Jumper open |
|
|
|
|
|
| |
|
|
|
|
|
| Jumper closed |
|
|
|
|
|
| |
|
|
|
|
|
| |
|
|
|
|
|
|
|
| SW1 is not used. Module RIUP is not affected by using the RTP. | |||||
| See page 203 for RTP internal schematic. |
| ||||
|
|
|
|
|
|
|