Honeywell HC900 manual Terminal Block Wiring Diagrams, Isolation, RTD Inputs, OHMs Inputs

Models: HC900

1 228
Download 228 pages 17.95 Kb
Page 78
Image 78

I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams

I/O Terminal Block Wiring Diagrams

Universal Analog Input Module Wiring

The Universal Analog Input Module has eight inputs, which can include any combination of the following input types: RTD, TC, Ohms, Millivolt, Volt, or Milliamp. Figure 31 shows wiring examples of each of the analog input types. An example of wiring for eight TC inputs is given in Figure 33.

Specifications for this module and for other modules are given in the Specifications section of this manual.

Isolation

This module has eight inputs, which are isolated except for RTD current sources.

RTD Inputs

RTD inputs share current sources (two RTD inputs per source), as shown in Figure 30, in Figure 31, and in Figure 32.

For example, the current source for the RTD input at channel one (terminals 1 and 2) is terminal 3 (IRTD 1 & 2). This same current source (IRTD 1 & 2) is also used for an RTD input at channel two (terminals 4 and 5).

Figure 32 and Figure 35 show examples of RTD input wiring (2-wire and 3-wire RTDs). Four-wire RTD inputs are not available).

Figure 30 - RTD Inputs

OHMs Inputs

Ohms inputs are wired similar to 2-wire RTD inputs. That is, they require a current source, and thus must use one of the IRTD current sources. Also, two terminals are jumpered together as they are for two-wire RTD inputs.

Analog channels wired for Ohms inputs differ from RTD inputs in these aspects:

Ohms inputs connect to variable resistance devices other than RTDs, and

Ohms inputs are configured in Hybrid Control Designer as Ohms inputs, rather than as RTD inputs. Examples of wiring for resistance inputs are given in Figure 34.

Shield Grounding

Shields must be grounded as described under Shield Grounding at the beginning of this section.

Hazardous voltages exist at terminal blocks.

Using switches at field devices, disconnect the field wiring from power sources before servicing.

Failure to comply with these instructions could result in death or serious injury.

68

HC900 Hybrid Controller Installation and User Guide

Revision 5

 

 

9/03

Page 78
Image 78
Honeywell HC900 manual Terminal Block Wiring Diagrams, Isolation, RTD Inputs, OHMs Inputs, Shield Grounding