Appendix B Installation of Remote Termination Panels (RTPs) - Analog Input
Analog Input
8 Point Analog Input
Step | Action |
|
|
1 | ATTENTION: RTP is not for use with thermocouples. |
| ATTENTION: RTP and cables are intended for permanent installation within their own enclosure. |
| Mount RTP cable assembly to HC900 Controller (Figure 60). |
| • Remove appropriate key tabs from terminal block to allow mating with the module. See page 64. |
| • Connect desired cable to AI module at controller. Choose from: |
| |
| |
| |
| • Install AI module label onto the module connector cover. |
| • Connect shield drain wire to the grounding bars at the base of the HC900 rack. All |
| shields must be grounded as described in the shield grounding section (page 60). |
|
|
2 | Mount RTP to DIN rail. |
| • Latch to rail. See page 205. |
| • Connect cable to RTP. |
|
|
184 | HC900 Hybrid Controller Installation and User Guide | Revision 5 |
|
| 9/03 |