Honeywell HC900 manual Contact Input Module Wiring, Internally Powered Input Channels

Models: HC900

1 228
Download 228 pages 17.95 Kb
Page 87
Image 87

I/O Module Installation and Wiring - I/O Terminal Block Wiring Diagrams

Contact Input Module Wiring

The Contact Input Module has sixteen inputs in one group. An example of Contact Input wiring is shown in Figure 42

Specifications for the Contact Input Module and other modules are given in the Specifications section of this manual.

Internally Powered Input Channels

The Contact Input Module provides voltage to the field contacts.

CAUTION

Do not apply any external power to the field device or to the input terminals. Doing so could damage the module.

Common terminals

Four common terminals are provided for the 16 inputs. Terminals 9, 10, 11, and 12 are connected in the Contact Input module.

Hazardous voltages exist at terminal blocks.

Using switches at field devices, disconnect the field wiring from power sources before servicing.

Failure to comply with these instructions could result in death or serious injury.

Figure 42 - Contact Input Wiring Diagram

Revision 5

HC900 Hybrid Controller Installation and User Guide

77

9/03

 

 

Page 87
Image 87
Honeywell HC900 manual Contact Input Module Wiring, Internally Powered Input Channels