Diagnostics and Troubleshooting - User Interface
Table 27 - Controller Module Diagnostics
OI Screen | OI Screen | Number of | Possible Cause | Control File Action | User Action |
Item | Item Value | LED |
|
|
|
|
| Strobes |
|
|
|
MODULE 1 | GOOD | N/A | N/A | N/A | N/A |
through |
|
|
|
|
|
MODULE 16 |
|
|
|
|
|
| HI CJ | 6 | Possible causes of | 1. Associated AI blocks | 1. Improve ventilation |
| TEMPERAT |
| this diagnostic are: | that are configured as | to rack |
| URE |
| 1. One of the two CJs | T/Cs set their fail pin | 2. Replace AI module |
|
|
| on, their warn pin off, | ||
|
|
| on the module is |
| |
|
|
| and their output pin to |
| |
|
|
| indicating a |
| |
|
|
| the failsafe value. |
| |
|
|
| temperature reading |
| |
|
|
| 2. Associated AI blocks |
| |
|
|
| greater than 70 |
| |
|
|
| degrees C. | that are configured as |
|
|
|
| 2. Both | T/Cs set their IO status |
|
|
|
| to “CJ High |
| |
|
|
| sensors are failing to |
| |
|
|
| Temperature” for |
| |
|
|
| convert. |
| |
|
|
| reason 1 or “CJ Failure” |
| |
|
|
| 3. The CJs are |
| |
|
|
| for possible causes 2 |
| |
|
|
| converting properly, | and 3. |
|
|
|
| but their differential | 3. Associated rack |
|
|
|
| is greater than 10 |
| |
|
|
| monitor block’s module |
| |
|
|
| degrees C. |
| |
|
|
| fail pin is turned on. |
| |
|
|
|
|
| |
|
|
|
| 4. Associated rack |
|
|
|
|
| monitor block’s RACK |
|
|
|
|
| OK pin is turned off. |
|
|
|
|
| 5. Associated rack |
|
|
|
|
| monitor block’s |
|
|
|
|
| HITEMP pin is turned |
|
|
|
|
| on. |
|
|
|
|
| 6. ASYS block’s HITEMP |
|
|
|
|
| pin is turned on. |
|
|
|
|
| 7. ASYS block’s HW OK |
|
|
|
|
| pin is turned off. |
|
| WRONG | 6 | The module does not | 1. Associated blocks set | 1. Verify configuration |
| MODULE |
| agree with the module | their fail pin on, their | 2. Replace module with |
|
|
| required for the | warn pin off, and their | |
|
|
| the correct one. | ||
|
|
| control scenario. | output pin to the | |
|
|
|
| ||
|
|
|
| failsafe value. |
|
|
|
|
| 2. Associated blocks set |
|
|
|
|
| their IO status to |
|
|
|
|
| “Channel No Comm”. |
|
|
|
|
| 3. Associated rack |
|
|
|
|
| monitor block’s module |
|
|
|
|
| fail pin is turned on. |
|
|
|
|
| 4. Associated rack |
|
|
|
|
| monitor block’s RACK |
|
|
|
|
| OK pin is turned off. |
|
|
|
|
| 5. ASYS block’s HW OK |
|
|
|
|
| pin is turned off. |
|