Diagnostics and Troubleshooting - User Interface

Table 27 - Controller Module Diagnostics

OI Screen

OI Screen

Number of

Possible Cause

Control File Action

User Action

Item

Item Value

LED

 

 

 

 

 

 

 

Strobes

 

 

 

 

 

MODULE 1

MODULE NO

6

Main CPU is unable to

See WRONG MODULE.

Action is based on the

through

COMM

 

communicate to the

 

IODIAG indication. If

MODULE 16

 

 

module for one of the

 

IODIAG is not

 

 

 

following reasons:

 

MODULE ERROR,

 

 

 

Module is not

 

then follow the

 

 

 

 

prescribed action

 

 

 

 

installed

 

 

 

 

 

 

defined for that

 

 

 

 

Backplane problem

 

 

 

 

 

diagnostic.

 

 

 

 

is inhibiting the

 

For MODULE ERROR,

 

 

 

 

CPU to properly

 

 

 

 

 

 

 

do the following:

 

 

 

 

communicate with

 

 

 

 

 

 

 

1.

Verify configuration

 

 

 

 

the module

 

 

 

 

Module is on an

 

2.

Install module.

 

 

 

 

expansion

 

 

 

 

 

 

 

rack(C50 CPU

 

 

 

 

 

 

 

only) and the

 

 

 

 

 

 

 

expansion rack

 

 

 

 

 

 

 

communications is

 

 

 

 

 

 

 

failing

 

 

 

 

BAD

6

See Table 29 - Bad

Associated block sets its

See Table 29 - Bad

 

CHANNEL

 

Channel Diagnostics.

fail pin on, its warn pin

Channel Diagnostics.

 

 

 

 

 

off, and its output pin to

 

 

 

 

 

 

 

the failsafe value.

 

 

 

 

 

 

 

Associated block sets its

 

 

 

 

 

 

 

IO status as denoted in

 

 

 

 

 

 

 

Table 29 - Bad Channel

 

 

 

 

 

 

 

Diagnostics.

 

 

 

 

 

 

 

Associated rack monitor

 

 

 

 

 

 

 

block’s module fail pin is

 

 

 

 

 

 

 

turned on.

 

 

 

 

 

 

 

Associated rack monitor

 

 

 

 

 

 

 

block’s RACK OK pin is

 

 

 

 

 

 

 

turned off.

 

 

 

 

 

 

 

ASYS block’s HW OK

 

 

 

 

 

 

 

pin is turned off.

 

 

 

BAD

6

Module is reporting a

See WRONG MODULE.

User should inspect

 

MODULE

 

diagnostic condition.

 

the module’s status

 

 

 

See Table 28 - Bad

 

LED to determine the

 

 

 

Module Diagnostics.

 

nature of the problem.

 

 

 

 

 

 

The information in

 

 

 

 

 

 

Table 28 - Bad

 

 

 

 

 

 

Module Diagnostics

 

 

 

 

 

 

describes the user

 

 

 

 

 

 

action for the various

 

 

 

 

 

 

LED diagnostics.