Diagnostics and Troubleshooting - User Interface
Table 30 - Scanner Diagnostics
Diagnostic | Number | Possible Cause | Scanner Action | User Action |
Condition | of |
|
|
|
| Strobes |
|
|
|
|
|
|
|
|
Watchdog Reset | 3 | Watchdog reset resulting from | Scanner restarts and | 1. Cycle power to the scanner |
|
| software failure | requests configuration | 2. Upgrade scanner software |
|
|
| from the main CPU. | |
|
|
|
| 3. Replace scanner module |
|
|
|
| 4. Contact Honeywell Personnel. |
|
|
|
|
|
Prefetch abort | 3 | CPU failed when attempting to | See watchdog reset | 1. Cycle power to the scanner |
CPU exception |
| fetch an instruction from the |
| 2. Isolate system from noise and |
|
| prefetch register. |
| |
|
|
|
| cycle power to the scanner |
|
|
|
| 3. Replace scanner module |
|
|
|
|
|
Address error | 3 | The reserved exception | See watchdog reset | See Prefetch abort CPU |
CPU exception |
| occurred for an unknown |
| exception |
|
| reason. |
|
|
|
|
|
|
|
Undefine | 3 | Bad Instruction Detected | See watchdog reset | See Prefetch abort CPU |
instruction CPU |
|
|
| exception |
exception |
|
|
|
|
|
|
|
|
|
Data abort CPU | 3 | CPU failed when attempting to | See watchdog reset | See Prefetch abort CPU |
exception |
| access data. |
| exception |
|
|
|
|
|
Software interrupt | 3 | Spurious Interrupt | See watchdog reset | See Prefetch abort CPU |
exception |
|
|
| exception |
|
|
|
|
|
Vector error | 3 | Interrupt vectors in RAM were | Interrupt vectors were | See Watchdog reset |
|
| corrupted | restored |
|
|
|
|
|
|
Flash write error | 4 | Flash failed to burn properly. | The boot code is the | Do a code download. |
|
|
| only software running. |
|
|
|
| This software waits |
|
|
|
| for a request to burn |
|
|
|
| the flash. It does no |
|
|
|
| scanning of modules. |
|
|
|
| Modules remain in |
|
|
|
| their failsafe state. |
|
|
|
|
|
|
Rack backplane | 6 | The Scanner is unable to | Does no scanning of | 1. Remove modules and check |
failure |
| successfully communicate to | modules. Modules | for bent pins on connectors. |
|
| any modules that are in its SPI | remain in their failsafe | 2. Reinsert modules one at a time |
|
| backplane. | state. | |
|
|
|
| and note which module the |
|
|
|
| diagnostic reoccurs, and |
|
|
|
| replace that module. |
|
|
|
| 3. Cycle power to the rack. |
|
|
|
| 4. Replace the power supply. |
|
|
|
| 5. Replace the rack. |
|
|
|
| 6. Replace the scanner module. |
|
|
|
|
|