Lennox International Inc SL280UH090V36B Return Air −− Upflow Applications, Side View

Models: SL280UH090V36B SL280UH070V36A DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE UPFLOW / HORIZONTAL AIR DISCHARGE SL280UH090V48B

1 72
Download 72 pages 31.79 Kb
Page 10
Image 10
Return Air −− Upflow Applications

Return Air −− Upflow Applications

Return air can be brought in through the bottom or either side of the furnace installed in an upflow application. If the furnace is installed on a platform with bottom return, make an airtight seal between the bottom of the furnace and the platform to ensure that the furnace operates properly and safely. The furnace is equipped with a removable bottom panel to facilitate installation.

Markings are provided on both sides of the furnace cabinet for installations that require side return air. Cut the furnace cabinet at the maximum dimensions shown on page 2.

NOTE − 60C and 60D units that require air volumes over 1800

cfm (850 L/s) must have one of the following:

1 − Return air from single side with transition which will accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) clean- able air filter. (Required to maintain proper air velocity.) See figure 8.

2 − Return air from single side with optional RAB Return Air Base. See figure 9.

3 − Return air from bottom and one side.

4 − Return air from both sides.

5 − Return air from bottom.

Refer to Engineering Handbook for additional information.

Single Side Return Air

(with transition and filter)

20” X 25” X 1”

(508mm X635mm X 25mm)

Cleanable Filter

Return Air

Plenum

AIR FLOW

Transition

FIGURE 8

Optional Return Air Base

(Upflow Applications Only −− For use with A, B, C and D cabinets)

 

FURNACE

 

 

FRONT

 

 

 

IF BASE

3−1/4

 

 

IS USED

 

 

WITHOUT

(83)

 

INDOOR AIR

IAQ CABINET,

 

 

A SINGLE

 

 

 

RETURN AIR

 

 

 

PLENUM

 

AIR FLOW

 

MUST

 

 

COVER BOTH

 

 

 

 

 

 

UNIT AND

 

 

 

RETURN

 

 

 

AIR BASE

7−1/4

 

 

OPENINGS

(184)

14−1/2” (368) A Width (65W75)

OPTIONAL

 

 

17−1/2” (446) B Width (50W98)

RETURN AIR BASE

 

21”− (533) C Width (50W99)

24−1/2”− (622) D Width (51W00)

1 23 (584)

 

 

 

 

Overall

 

 

 

 

 

 

 

 

 

(Maximum)

1 Minimum

 

 

 

11 (279)

 

1 Unit side return air

2 Maximum

14 (356)

 

Opening

 

 

 

 

 

 

 

 

 

 

 

 

 

5−5/8

SIDE RETURN

 

 

 

 

AIR OPENINGS

 

 

 

(143)

 

 

 

(Either Side)

 

 

 

 

 

 

 

 

 

 

 

 

23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(584)

 

 

 

 

 

 

 

 

26−7/8

 

 

 

 

 

 

(683)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SIDE VIEW

 

 

 

122−7/16

(570)

Overall

(Maximum)

3/4

(19)

NOTE− Optional Side Return Air Filter Kits are not for use with Optional Return Air Base.

1Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.

Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm). The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.

Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air

opening. The size of the opening must not extend beyond the markings on the furnace cabinet.

2To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.

FIGURE 9

Page 10

Page 10
Image 10
Lennox International Inc SL280UH090V36B, SL280UH090V48B, SL280UH070V36A Return Air −− Upflow Applications, Side View