Integrated Control Diagnostic Codes (continued)

E 272

Soft lockout − Exceeded maximum number of recycles. Last recycle due

Check operation of low pressure switch to see if it is

 

to the pressure switch opening.

stuck closed on heat call. Check pressure (inches

 

 

w.c.) of high pressure switch closing on heat call.

 

 

Measure operating pressure (inches w.c.). Inspect

 

 

vent and combustion air inducer for correct opera-

 

 

tion and restriction. Clears when heat call finishes

 

 

successfully.

 

 

 

E 273

Soft lockout − Exceeded maximum number of recycles. Last recycle due

Check micro−amperes of flame sensor using control

 

to flame failure.

diagnostics or field−installed mode. Clean or replace

 

 

sensor. Measure voltage of neutral to ground to en-

 

 

sure good unit ground. Clears when heat call finish-

 

 

es successfully.

 

 

 

E 274

Soft lockout − Exceeded maximum number of recycles. Last recycle

Shut down system. 1−hour soft lockout. Check firing

 

failed due to the limit circuit opening or limit remained open longer than

rate and air flow. Check for blockage. Clears when

 

3 minutes.

heat call finishes successfully.

 

 

 

E 275

Soft lockout − Flame sensed out of sequence. Flame signal is gone.

Shut off gas. Check for gas valve leak. 1−hour soft

 

 

lockout. Clears when flame has been proven stable.

 

 

 

E 276

Watchguard calibration failure.

Unable to perform pressure switch calibration.

 

 

Check vent system and pressure switch wiring con-

 

 

nections. 1−hour soft lockout. Clears when calibra-

 

 

tion has finished successfully.

 

 

 

E 290

Ignitor circuit fault − Failed ignitor or triggering circuitry.

Measure resistance of hot surface ignitor. Replace if

 

 

open or not within specifications. 1−hour soft lock-

 

 

out. Clears when flame has been proven stable.

 

 

 

E 291

Heat air flow restricted below the minimum.

Check for dirty filter and air flow restriction. Check

 

 

blower performance. 1−hour soft lockout. Cleared

 

 

when heat call finishes successfully.

 

 

 

E 292

Indoor blower motor unable to start due to obstructed wheel, seized

Indoor blower motor unable to start (seized bear-

 

bearings.

ing, stuck wheel, etc.). Replace motor or wheel if

 

 

assembly does not operate or meet performance

 

 

standards. 1−hour soft lockout. Clears after circula-

 

 

tor successfully starts.

 

 

 

E 294

Combustion air inducer over current.

Check combustion blower bearings, wiring and

 

 

amps. Replace if does not operate or does not meet

 

 

performance standards. Clears after inducer current

 

 

is sensed to be in−range after the ignition following

 

 

the soft lockout or reset.

 

 

 

E 295

Indoor blower motor temperature is too high.

Indoor blower motor over temperature (motor

 

 

tripped on internal protector). Check motor bearings

 

 

and amps. Replace if necessary. Cleared after

 

 

blower demand is satisfied.

 

 

 

E 310

Discharge error temperature sensor failure. Only shown if shorted or

Compare outdoor sensor resistance to temperature/

 

out of range.

resistance charts in installation instructions. Re-

 

 

place sensor if necessary. Cleared in Communicat-

 

 

ing mode: 30 seconds after fault recovered. In Non−

 

 

Communicating mode: Cleared after the current

 

 

heat call is completed.

 

 

 

E 311

Heat rate reduced to match indoor blower air flow.

Warning Only. Furnace blower in cutback mode due

 

 

to restricted airflow. Reduce firing rate every 60

 

 

seconds to match available CFM. Check filter and

 

 

duct system. To clear, replace filter if needed or re-

 

 

pair/add duct. 2−stage controls will reduce firing rate

 

 

to 1st stage. Clears when heat call finishes success-

 

 

fully.

 

 

 