Integrated Control Diagnostic Codes (continued)

Code

Diagnostic Codes/Status of Equipment

Action Required to Clear and Recover

 

 

 

E 105

Device communication problem − No other devices on RS BUS (Commu-

Equipment is unable to communicate. Indicates

 

nication

numerous message errors. In most cases errors are

 

system).

related to electrical noise. Make sure high voltage

 

 

power is separated from RSBus. Check for mis−

 

 

wired and/or loose connections between the stat,

 

 

indoor unit and outdoor unit. Check for a high volt-

 

 

age source of noise close to the system. Fault

 

 

clears after communication is restored.

 

 

 

E 110

Low line voltage.

Line Voltage Low (Voltage lower than nameplate

 

 

rating). Check power line voltage and correct. Alarm

 

 

clears 5 seconds after fault recovered.

 

 

 

E 111

Line voltage polarity reversed.

Reverse line power voltage wiring. System resumes

 

 

normal operation 5 seconds after fault recovered.

 

 

 

E 112

Ground not detected

System shuts down. Provide proper earth ground.

 

 

System resumes normal operation 5 seconds after

 

 

fault recovered.

 

 

 

E 113

High line voltage.

Line Voltage High (Voltage higher than nameplate

 

 

rating). Provide power voltage within proper range.

 

 

System resumes normal operation 5 seconds after

 

 

fault recovered.

 

 

 

E 114

Line voltage frequency out−of−range.

No 60 Hertz Power. Check voltage and line power

 

 

frequency. Correct voltage and frequency problems.

 

 

System resumes normal operation 5 seconds after

 

 

fault recovered.

 

 

 

E 115

Low 24V − Control will restart if the error recovers.

24−Volt Power Low (Range is 18 to 30 volts). Check

 

 

and correct voltage. Check for additional power−rob-

 

 

bing equipment connected to system. May require

 

 

installation of larger VA transformer to be installed in

 

 

furnace / air handler. Clears after fault recovered.

 

 

 

E 116

High 24V.

24 Volt Power High (Range is 18 to 30 volts). Check

 

 

and correct voltage. Check for proper line voltage

 

 

(120V, 240V, etc.) to equipment. Clears when con-

 

 

trol senses proper voltage.

 

 

 

E 117

Poor ground detected (Warning only)

Provide proper grounding for unit. Check for proper

 

 

earth ground to the system. Warning only will clear

 

 

30 seconds after fault recovered.

 

 

 

E 120

Unresponsive device. Communication only.

Usually caused by delay in outdoor unit responding

 

 

to indoor unit poling. Recycle power. Check all wir-

 

 

ing connections. Cleared after unresponsive device

 

 

responds to any inquiry.

 

 

 

E 124

Active communicating thermostat signal missing for more than 3 min-

Equipment lost communication with the thermostat.

 

utes.

Check four wiring connections, ohm wires and cycle

 

 

power at the thermostat. Alert stops all services and

 

 

waits for heartbeat message from thermostat (sub-

 

 

net controller). Cleared after valid thermostat (sub-

 

 

net controller) message is received.

 

 

 

E 125

Control failed self−check, internal error, failed hardware. Will restart if

Hardware problem on the control. Cycle power on

 

error

control. Replace if problem prevents service and is

 

recovers. Integrated control not communicating. Covers hardware errors

persistent. Critical alert. Cleared 300 seconds after

 

(flame sense circuit faults, pin shorts, etc.).

fault recovered.

 

 

 

E 126

Control internal communication problem.

Hardware problem on the control. Cycle power on

 

 

control. Replace if problem prevents service and is

 

 

persistent. Cleared 300 seconds after fault recov-

 

 

ered.

 

 

 