Lennox International Inc SL280UH090V48B, SL280UH070V36A Program Unit Capacity/Size Mode

Models: SL280UH090V36B SL280UH070V36A DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE UPFLOW / HORIZONTAL AIR DISCHARGE SL280UH090V48B

1 72
Download 72 pages 31.79 Kb
Page 67
Image 67
Program Unit Capacity/Size Mode

Program Unit Capacity/Size Mode

Power−Up − Number displayed represents by integrated control unit size code (furnace model and capacity). If three horizontal bars are displayed followed by continuous E203, furnace control does not recognize unit size code. Configure per the following:

 

 

Yes

To enter Program Unit

 

Capacity/Size: push

 

and hold button next to

_

7−segment LED display

 

until solid

symbol

 

appears.

Release

 

button.

 

 

IMPORTANT: Field replacement controls may need to be manually configured to validate furnace unit size code.

Solid P

starts

 

P

blinking

on

 

7−Segment LED

Push and hold button. Integrated control will display unit size code number for each furnace model for three seconds.

Furnace control in IDLE mode

No heating, cooling or indoor fan No operation)

Turn room thermostat to OFF

UNIT SIZE

 

UNIT SIZE

 

CODE

FURNACE MODEL

CODE

FURNACE MODEL

A

SL280UH070V36A

A

SL280DF070V36A

b

SL280UH090V36B

b

SL280DF090V48B

C

SL280UH090V48B

C

SL280DF090V60C

d

SL280UH090V60C

d

SL280DF110V60C

E

SL280UH110V60C

 

 

F

SL280UH135V60D

 

 

 

 

 

 

When the correct unit size code is displayed, release button. Selected code will flash for 10−second period. During that period, press and hold push button for 5 seconds. Integrated control will store code in memory and will automatically exit Program Unit Capacity/Size Mode and reset. (If second period expires or push button is held less than five seconds, control will automatically exit Program Capacity/Size Mode and go into IDLE mode without storing unit size code. If this happens, programming function must be repeated).

Verify that the selected unit size code is correct and stored in non−volatile memory by cycling the 24 volt power to the furnace control. (At 24 volt power−up of the furnace control, the 7−segment LED will display a unit size code. If three horizontal bars display, board does not recognize unit size code. Programming function must be repeated)

FINISHED