Lennox International Inc SL280UH070V36A, SL280UH090V48B Table Operating Sequence, Page

Models: SL280UH090V36B SL280UH070V36A DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE UPFLOW / HORIZONTAL AIR DISCHARGE SL280UH090V48B

1 72
Download 72 pages 31.79 Kb
Page 49
Image 49

TABLE 18

OPERATING SEQUENCE

SL280UHV, Non−Communicating Thermostat with Humidity Control Feature and Single−Speed Outdoor Unit

OPERATING

 

 

 

SYSTEM DEMAND

 

 

SYSTEM RESPONSE

SEQUENCE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermostat Demand

 

Relative Humidity

 

Blower

 

System

 

 

 

 

 

 

 

 

 

Compres-

 

Step

 

 

 

W

 

 

 

 

CFM

Comments

Condition

Y1

O

G

 

 

Status

D

sor

 

1

 

 

(COOL)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO CALL FOR DEHUMIDIFICATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24

 

 

Compressor and indoor

Normal Operation

1

On

On

On

 

 

 

Acceptable

High

100%

blower follow thermostat

 

 

 

VAC

 

 

 

 

 

 

 

 

 

 

 

demand

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BASIC MODE (only active on a Y1 thermostat demand)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal Operation

1

On

On

On

 

 

 

Acceptable

24

High

100%

ComfortSense® 7000

 

 

 

 

 

 

 

 

 

VAC

 

 

thermostat energizes Y1

 

 

 

 

 

 

 

 

 

 

 

 

Dehumidification

2

On

On

On

 

 

 

Demand

0

High

70%*

and de−energizes D on a

Call

 

 

 

VAC

call for de−humidification

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRECISION MODE (operates independent of a Y1 thermostat demand)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal Operation

1

On

On

On

 

 

 

Acceptable

24

High

100%

 

 

 

 

VAC

Dehumidification mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

begins when humidity is

Dehumidification

 

 

 

 

 

 

 

 

0

 

 

2

On

On

On

 

 

 

Demand

High

70%*

greater than set point

call

 

 

 

VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dehumidification

 

 

 

 

 

 

 

 

0

 

 

ComfortSense® 7000

1

On

On

On

 

 

 

Demand

High

70%*

thermostat will try to

call ONLY

 

 

 

VAC

 

 

 

 

 

 

 

 

 

 

maintain room humidity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setpoint by allowing the

 

Jumpers at indoor unit with a single stage outdoor unit

 

 

 

 

 

room space to maintain a

 

With Condensing unit − Cut W914 (R to DS) on SureLight® control

 

 

 

cooler room thermostat

 

With Heat Pump − Cut W914 (R to DS) & W951 (R to O) on SureLight® control

 

setpoint**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dave Lennox ComfortSense® 7000 thermostat to use for this application − Y2081 4 heat / 2 cool *Dehumidification blower speed is 70% of COOL speed for all units .

**In Precision mode, ComfortSense® 7000 thermostat will maintain room temperature up to 2 °F (1.2°C) cooler than room setting.

Page 49

Page 49
Image 49