18− Reconnect all wires.
19− Reconnect top cap and vent pipe to combustion air in- ducer outlet.
20− Reconnect gas supply piping.
21− Turn on power and gas supply to unit.
22− Set thermostat and check for proper operation.
23− Check all piping connections, factory and field, for gas leaks. Use a leak detecting solution or other preferred means.
CAUTION
Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly af- ter leak test has been completed. Do not use matches, candles, flame or other sources of ignition to check for gas leaks.
24− If a leak is detected, shut gas and electricity off and repair leak.
25− Repeat steps 24 and 26 until no leaks are detected.
26− Replace access panel.