Lennox International Inc SL280UH090V36B Other Unit Adjustments, Heating Sequence of Operation

Models: SL280UH090V36B SL280UH070V36A DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE UPFLOW / HORIZONTAL AIR DISCHARGE SL280UH090V48B

1 72
Download 72 pages 31.79 Kb
Page 54
Image 54
Other Unit Adjustments

Other Unit Adjustments

Primary and Secondary Limits

The primary limit is located on the heating compartment vestibule panel. The secondary limits (if equipped) are lo- cated in the blower compartment, attached to the back side of the blower. These auto reset limits are factory set and re- quire no adjustment.

Flame Rollout Switches (Two)

These manually reset switches are located on (or inside of) the burner box. If tripped, check for adequate combustion air before resetting.

Pressure Switches

The pressure switch assembly (includes two switches) is located in the heating compartment adjacent to the com- bustion air inducer. These switches check for proper com- bustion air inducer operation before allowing ignition trial. The switches are factory−set and require no adjustment.

Temperature Rise

Place the unit into operation with a second−stage heating demand. After supply and return air temperatures have stabilized, check the temperature rise. If necessary, adjust the heating blower speed to maintain the temperature rise within the range shown on the unit nameplate. Increase the blower speed to decrease the temperature rise. Decrease the blower speed to increase the temperature rise. Failure to properly adjust the temperature rise may cause erratic limit operation.

Thermostat Heat Anticipation

Set the heat anticipator setting (if adjustable) according to the amp draw listed on the wiring diagram that is attached to the unit.

NOTE − Do not secure the electrical conduit directly to the air ducts or structure.

Heating Sequence of Operation

Electronic Ignition

The two−stage, variable speed integrated control used in SL280UHV units has an added feature of an internal Watch- guard control. The feature serves as an automatic reset de- vice for ignition control lockout caused by ignition failure. Af- ter one hour of continuous thermostat demand for heat, the Watchguard will break and remake thermostat demand to the furnace and automatically reset the control to begin the ignition sequence.

NOTE − The ignition control thermostat selection DIP switch is factory−set in the AGE" position.

Applications Using a Two−Stage Thermostat See figure 37 for ignition control sequence

A − Heating Sequence −− Integrated Control Thermostat Selection DIP Switch 1 OFF in wo−Stage" Position (Factory Setting)

1 − On a call for heat, thermostat first−stage contacts close sending a signal to the integrated control. The inte- grated control runs a self-diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts. The combustion air inducer is ener- gized at low speed.

2 − Once the control receives a signal that the low pres- sure switch has closed, the combustion air inducer be- gins a 15−second pre−purge in low speed.

NOTE − If the low fire pressure switch does not close the combustion air inducer will switch to high fire. After a 15 second pre−purge the high fire pressure switch will close and the unit will begin operation on high fire. After 10 to 20 seconds of high fire operation the unit will switch to low fire..

3 − After the pre−purge is complete, a 20−second initial ig- nitor warm−up period begins. The combustion air in- ducer continues to operate at low speed.

4 − After the 20−second warm−up period has ended, the gas valve is energized on low fire (first stage) and ignition oc- curs. At the same time, the control module sends a sig- nal to begin an indoor blower 30−second ON−delay. When the delay ends, the indoor blower motor is ener- gized on the low fire heating speed, the HUM contacts close energizing the humidifier and 120V ACC termi- nal is energized. The furnace will continue this opera- tion as long as the thermostat has a first−stage heating demand.

5 − If second−stage heat is required, the thermostat sec- ond−stage heat contacts close and send a signal to the integrated control. The integrated control initiates a 30−second second−stage recognition delay.

6 − At the end of the recognition delay, the integrated con- trol energizes the combustion air inducer at high speed. The control also checks the high fire (second stage) pressure switch to make sure it is closed. The high fire (second stage) gas valve is energized and the indoor blower motor is energized for operation at the high fire heating speed.

7 − When the demand for high fire (second stage) heat is satisfied, the combustion air inducer is switched to the low−fire heating speed and the high−fire (second stage) gas valve is de−energized. The low−fire (first stage) gas valve continues operation. The indoor blower motor is switched to the low−fire heating speed.

8 − When the thermostat demand for low−fire (first stage) heat is satisfied, the gas valve is de−energized and the field−selected indoor blower off delay begins. The combustion air inducer begins a 5−second post−purge period.

9 − When the combustion air post−purge period is com- plete, the inducer, the HUM contacts as well as the 120V ACC terminals are de−energized. The indoor blower is de−energized at the end of the off delay.

Page 54

Page 54
Image 54
Lennox International Inc SL280UH090V36B, SL280UH090V48B Other Unit Adjustments, Heating Sequence of Operation