Lennox International Inc SL280UH090V48B, SL280UH070V36A Blower Data, Heating, Cooling

Models: SL280UH090V36B SL280UH070V36A DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE UPFLOW / HORIZONTAL AIR DISCHARGE SL280UH090V48B

1 72
Download 72 pages 31.79 Kb
Page 43
Image 43
Manual background

BLOWER DATA

SL280UH090V60C BLOWER PERFORMANCE (less filter)

BOTTOM RETURN AIR, RETURN AIR FROM BOTH SIDES OR RETURN AIR FROM BOTTOM AND ONE SIDE 0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

HEATING

1 Heating Speed

 

 

 

 

 

 

 

 

 

 

 

DIP Switch

 

First Stage Heating Speed - cfm

 

 

Second Stage Heating Speed - cfm

 

Settings

 

 

 

 

 

 

 

 

 

 

 

+24%

 

1420

 

 

 

1565

 

 

+18%

 

1355

 

 

 

1490

 

 

+12%

 

1285

 

 

 

1415

 

 

+6%

 

1215

 

 

 

1335

 

 

Factory Default

 

1145

 

 

 

1260

 

 

–6%

 

1080

 

 

 

1185

 

 

–12%

 

1010

 

 

 

1110

 

 

–18%

 

940

 

 

 

1035

 

 

 

 

 

COOLING

 

 

 

 

 

 

1 Cooling Speed

 

First Stage Cooling Speed - cfm

 

 

Second Stage Cooling Speed - cfm

 

DIP Switch

Low

Medium-Low

Medium-High

 

2 High

Low

 

Medium-Low

Medium-High

 

2 High

Settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

1110

1205

1420

 

1680

1575

 

1740

2000

 

2305

Factory Default

1005

1100

1280

 

1545

1440

 

1595

1820

 

2125

890

1015

1125

 

1380

1295

 

1450

1610

 

1930

SINGLE SIDE RETURN AIR

0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

HEATING

1 Heating Speed

 

 

 

 

 

 

 

 

 

 

 

DIP Switch

 

First Stage Heating Speed - cfm

 

 

Second Stage Heating Speed - cfm

 

Settings

 

 

 

 

 

 

 

 

 

 

 

+24%

 

1360

 

 

 

1500

 

 

+18%

 

1295

 

 

 

1425

 

 

+12%

 

1230

 

 

 

1355

 

 

+6%

 

1165

 

 

 

1280

 

 

Factory Default

 

1100

 

 

 

1210

 

 

–6%

 

1030

 

 

 

1135

 

 

–12%

 

965

 

 

 

1065

 

 

–18%

 

900

 

 

 

990

 

 

 

 

 

COOLING

 

 

 

 

 

 

1 Cooling Speed

 

First Stage Cooling Speed - cfm

 

 

Second Stage Cooling Speed - cfm

 

DIP Switch

 

 

 

 

 

 

 

 

 

 

 

Low

Medium-Low

Medium-High

 

2 High

Low

 

Medium-Low

Medium-High

 

2 High

Settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

1050

1165

1335

 

1620

1515

 

1680

1915

 

2225

Factory Default

955

1060

1215

 

1480

1390

 

1545

1735

 

2060

840

945

1090

 

1290

1220

 

1385

1580

 

1825

1Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch Settings.

2Factory default setting.

NOTES - The effect of static pressure is included in air volumes shown.

First stage HEAT is approximately 91% of the same second stage HEAT.

First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 500 cfm. Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 480 cfm.