Integrated Control Diagnostic Codes (continued)

Code

Diagnostic Codes/Status of Equipment

Action Required to Clear and Recover

 

 

 

E 312

Restricted air flow in cooling or continuous fan mode is lower than cfm

Warning Only. Restricted airflow − Indoor blower is

 

setting.

running at a reduced CFM (Cutback Mode − The

 

 

variable speed motor has pre−set speed and torque

 

 

limiters to protect the motor from damage caused

 

 

by operating outside of design parameters (0 to 0.8"

 

 

W.C.. total external static pressure). Check filter and

 

 

duct system. To clear, replace filter if needed or re-

 

 

pair/add duct. Cleared after the current service de-

 

 

mand is satisfied.

 

 

 

E 313

Indoor or outdoor unit capacity mismatch. Communication only.

Incorrect indoor/outdoor capacity code selected.

 

 

Check for proper configuring in installation instruc-

 

 

tions. Alarm is just a warning. The system will oper-

 

 

ate, but might not meet efficiency and capacity pa-

 

 

rameters. Alarm will clear when commissioning is

 

 

exited. Cleared after commissioning is complete.

 

 

 

E 331

Global network connection − Communication link problem.

For Future Use.

 

 

 

E 334

Relay

Replace integrated control.

 

 

 

E 347

No 24 Volt output on Y1 of "integrated control" with non communicating

Operation stopped. Y1 relay / Stage 1 failed. (Pilot

 

outdoor unit.

relay contacts did not close or the relay coil did not

 

 

energize; no input back to IFC chip). Critical Alert.

 

 

Cleared after reset and Y1 input sensed.

 

 

 

E 348

No 24 Volt output on Y2 of "integrated control" with non?communicating

Y2 relay / Stage 2 failed. (Pilot relay contacts did

 

outdoor unit.

not close or the relay coil did not energize; no input

 

 

back to IFC chip). Critical Alert. Cleared after reset

 

 

and Y1 input sensed.

 

 

 

E 349

No 24 Volts between R & O on "integrated control" with non communi-

Configuration link R to O needs to be restored. Re-

 

cating outdoor unit (Dual fuel module required for heat pump application).

place link or hard−wire. Applicable in non communi-

 

 

cating mode. Critical Alert.

 

 

 

E 370

Interlock switch sensed open for 2 minutes.

Control sees the loss of 24VAC for 2 minutes .Ter-

 

 

minate all services and wait for interlock switch to

 

 

close. The alarm will clear when 24VAC is continu-

 

 

ously sensed on DS terminal for a minimum of 10

 

 

seconds or on a power reset.

 

 

 

E 400

LSOM − Compressor internal overload tripped.

Thermostat demand Y1 is present; but, compressor

 

 

is not running. Check power to outdoor unit. Clears

 

 

the error after current is sensed in both RUN and

 

 

START sensors for at least 2 seconds, or after ser-

 

 

vice is removed, or after power reset.

 

 

 

E 401

LSOM Compressor long run cycle or low system pressure.

Compressor ran more than 18 hours to satisfy a

 

 

single thermostat demand. Critical Alert. Clears the

 

 

error after 30 consecutive normal run cycles or

 

 

power reset. Also monitors low pressure switch

 

 

trips.

 

 

 

E 402

LSOM − Outdoor unit system pressure trip.

Discharge or suction pressure out−of−limits, or com-

 

 

pressor overloaded. Clears the error after 4 consec-

 

 

utive normal compressor run cycles.

 

 

 

E 403

LSOM − Compressor short−cycling. .(Running less than 4 minutes). Out-

Compressor runs less than 3 minutes to satisfy a

 

door unit pressure trip

thermostat demand. Clears the error after 4 consec-

 

 

utive normal run cycles or power reset.

 

 

 

E 404

LSOM − Compressor rotor locked. Compressor short−cycling. (Running

Compressor rotor locked up due to run capacitor

 

less than 4 minutes).

short, bearings are seized, excessive liquid refriger-

 

 

ant, etc. Clears the error after 4 consecutive normal

 

 

run cycles or after power reset.

 

 

 

E 405

LSOM − Compressor open circuit.

Compressor circuit open (due to power disconnec-

 

 

tion, open fuse, etc.) Clears the error after 1 normal

 

 

compressor run cycle.

 

 

 

Page 65

Page 65
Image 65
Lennox International Inc SL280UH070V36A Limiters to protect the motor from damage caused, Mand is satisfied