Lennox International Inc SL280UH070V36A Call For Second−Stage Heat, Call For Heat Satisfied

Models: SL280UH090V36B SL280UH070V36A DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE UPFLOW / HORIZONTAL AIR DISCHARGE SL280UH090V48B

1 72
Download 72 pages 31.79 Kb
Page 69
Image 69
CALL FOR SECOND−STAGE HEAT

Troubleshooting: Heating Sequence of Operation (Continued)

CALL FOR SECOND−STAGE HEAT

2

 

CALL FOR 2ND STAGE HEAT

1

 

 

 

 

(HIGH FIRE)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 STAGE THERMOSTAT

 

 

 

 

 

 

 

 

 

RECOGNITION DELAY

 

 

(30 SECONDS)

ONLY FOR 1ST EXPIRED?

REQUEST FOR

 

 

 

2ND STAGE HEAT

 

YES

 

 

 

 

 

 

 

SINGLE STAGE THERMOSTAT 2

2ND STAGE ON DELAY EXPIRED?

YES

INDUCER SWITCHED

TO HIGH SPEED

HIGH

 

 

 

 

 

 

 

PRESSURE SWITCH

 

 

 

 

INDUCER SWITCHED

 

 

 

NO

 

 

CLOSED WITHIN 10

 

 

 

TO LOW SPEED

 

 

 

 

 

 

SECONDS?

 

 

 

 

 

 

 

YES

2ND STAGE GAS VALVE

ENERGIZED

INDOOR BLOWER ENERGIZED

ON HIGH HEAT SPEED

3

CALL FOR HEAT SATISFIED

5 MINUTE DELAY

3

(ERROR CODE FLASHES)

1SYSTEM WILL ALWAYS LIGHT ON LOW FIIRE, EVEN IF 2ND STAGE HEAT IS IN PLACE.

2WHEN USED WITH A SINGLE STAGE THERMOSTAT, SET SW1 TO THE ON POSITION IN DIP SWITCH S4.

3IF THE HIGH FIRE PRESSURE SWITCH DOES NOT CLOSE WITHIN 5 ATTEMPTS, THE SYSTEM WILL OPERATE AT LOW FIRE FOR THE REMAINDER OF THE CALL FOR HEAT REQUEST.

Page 69

Page 69
Image 69
Lennox International Inc SL280UH070V36A, SL280UH090V48B, SL280UH090V36B Call For Second−Stage Heat, Call For Heat Satisfied