Lennox International Inc SL280UH070V36A, SL280UH090V48B Blower Data, Heating, Cooling

Models: SL280UH090V36B SL280UH070V36A DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE UPFLOW / HORIZONTAL AIR DISCHARGE SL280UH090V48B

1 72
Download 72 pages 31.79 Kb
Page 41
Image 41
Manual background

BLOWER DATA

SL280UH090V48B BLOWER PERFORMANCE (less filter)

BOTTOM RETURN AIR

0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

HEATING

1 Heating Speed

 

 

 

 

 

 

 

 

 

 

 

DIP Switch

 

First Stage Heating Speed - cfm

 

 

Second Stage Heating Speed - cfm

 

Settings

 

 

 

 

 

 

 

 

 

 

 

+24%

 

1280

 

 

 

1410

 

 

+18%

 

1220

 

 

 

1340

 

 

+12%

 

1155

 

 

 

1270

 

 

+6%

 

1095

 

 

 

1205

 

 

Factory Default

 

1035

 

 

 

1135

 

 

–6%

 

970

 

 

 

1070

 

 

–12%

 

910

 

 

 

1000

 

 

–18%

 

845

 

 

 

930

 

 

 

 

 

COOLING

 

 

 

 

 

 

1 Cooling Speed

 

First Stage Cooling Speed - cfm

 

 

Second Stage Cooling Speed - cfm

 

DIP Switch

Low

Medium-Low

Medium-High

 

2 High

Low

 

Medium-Low

Medium-High

 

2 High

Settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

670

890

1040

 

1210

1030

 

1335

1550

 

1755

Factory Default

605

815

965

 

1090

940

 

1205

1405

 

1,600

525

690

850

 

985

795

 

1060

1260

 

1435

SINGLE SIDE RETURN AIR

0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

HEATING

1 Heating Speed

 

 

 

 

 

 

 

 

 

 

 

DIP Switch

 

First Stage Heating Speed - cfm

 

 

Second Stage Heating Speed - cfm

 

Settings

 

 

 

 

 

 

 

 

 

 

 

+24%

 

1280

 

 

 

1410

 

 

+18%

 

1220

 

 

 

1340

 

 

+12%

 

1155

 

 

 

1270

 

 

+6%

 

1095

 

 

 

1205

 

 

Factory Default

 

1035

 

 

 

1135

 

 

–6%

 

970

 

 

 

1070

 

 

–12%

 

910

 

 

 

1000

 

 

–18%

 

845

 

 

 

930

 

 

 

 

 

COOLING

 

 

 

 

 

 

1 Cooling Speed

 

First Stage Cooling Speed - cfm

 

 

Second Stage Cooling Speed - cfm

 

DIP Switch

Low

Medium-Low

Medium-High

 

2 High

Low

 

Medium-Low

Medium-High

 

2 High

Settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

640

900

1015

 

1175

1005

 

1295

1500

 

1670

Factory Default

570

780

930

 

1040

895

 

1160

1345

 

1500

530

700

810

 

955

795

 

1050

1210

 

1405

1Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch Settings.

2Factory default setting.

NOTES - The effect of static pressure is included in air volumes shown.

First stage HEAT is approximately 91% of the same second stage HEAT.

First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 500 cfm. Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 455 cfm.

Page 41