Lennox International Inc SL280UH090V48B, SL280UH070V36A Blower Data, Heating, Cooling

Models: SL280UH090V36B SL280UH070V36A DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE UPFLOW / HORIZONTAL AIR DISCHARGE SL280UH090V48B

1 72
Download 72 pages 31.79 Kb
Page 39
Image 39
BLOWER DATA

BLOWER DATA

SL280UH070V36A BLOWER PERFORMANCE (less filter)

BOTTOM RETURN AIR

0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

HEATING

1 Heating Speed

 

 

 

 

 

 

 

 

 

 

 

DIP Switch

 

First Stage Heating Speed - cfm

 

 

Second Stage Heating Speed - cfm

 

Settings

 

 

 

 

 

 

 

 

 

 

 

+24%

 

1045

 

 

 

1145

 

 

+18%

 

985

 

 

 

1080

 

 

+12%

 

940

 

 

 

1035

 

 

+6%

 

880

 

 

 

960

 

 

Factory Default

 

850

 

 

 

925

 

 

–6%

 

785

 

 

 

875

 

 

–12%

 

745

 

 

 

815

 

 

–18%

 

680

 

 

 

745

 

 

 

 

 

COOLING

 

 

 

 

 

 

1 Cooling Speed

 

First Stage Cooling Speed - cfm

 

 

Second Stage Cooling Speed - cfm

 

DIP Switch

Low

Medium-Low

Medium-High

 

2 High

Low

 

Medium-Low

Medium-High

 

2 High

Settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

781

819

872

 

981

1045

 

1139

1219

 

1372

Factory Default

695

734

797

 

883

943

 

1005

1114

 

1260

645

674

720

 

815

847

 

922

991

 

1144

SINGLE SIDE RETURN AIR

0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

HEATING

1 Heating Speed

 

 

 

 

 

 

 

 

 

 

 

DIP Switch

 

First Stage Heating Speed - cfm

 

 

Second Stage Heating Speed - cfm

 

Settings

 

 

 

 

 

 

 

 

 

 

 

+24%

 

1050

 

 

 

1165

 

 

+18%

 

1000

 

 

 

1110

 

 

+12%

 

940

 

 

 

1040

 

 

+6%

 

895

 

 

 

975

 

 

Factory Default

 

820

 

 

 

935

 

 

–6%

 

775

 

 

 

855

 

 

–12%

 

735

 

 

 

805

 

 

–18%

 

685

 

 

 

750

 

 

 

 

 

COOLING

 

 

 

 

 

 

1 Cooling Speed

 

First Stage Cooling Speed - cfm

 

 

Second Stage Cooling Speed - cfm

 

DIP Switch

 

 

 

 

 

 

 

 

 

 

 

Low

Medium-Low

Medium-High

 

2 High

Low

 

Medium-Low

Medium-High

 

2 High

Settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

764

802

886

 

977

1035

 

1122

1248

 

1360

Factory Default

704

725

793

 

899

949

 

1029

1135

 

1257

642

680

717

 

812

874

 

933

1021

 

1133

1Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch Settings.

2Factory default setting.

NOTES - The effect of static pressure is included in air volumes shown.

First stage HEAT is approximately 91% of the same second stage HEAT.

First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 500 cfm. Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 425 cfm.

Page 39

Page 39
Image 39
Lennox International Inc DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE UPFLOW / HORIZONTAL AIR DISCHARGE Blower Data