Lennox International Inc SL280UH090V48B, SL280UH070V36A Integrated Control Diagnostic Modes

Models: SL280UH090V36B SL280UH070V36A DAVE LENNOX SIGNATURE COLLECTION GAS FURNACE UPFLOW / HORIZONTAL AIR DISCHARGE SL280UH090V48B

1 72
Download 72 pages 31.79 Kb
Page 60
Image 60
Integrated Control Diagnostic Modes

Integrated Control Diagnostic Modes

Display

Action (when button released)

 

 

No change (idle)*

Remain in idle mode

 

 

Solid

Enter diagnostic recall mode

 

 

Solid

Discharge Air Installed

 

 

Solid

Enter flame signal mode

 

 

Solid

Program unit capacity/size (Unit Code)**

 

 

*No change implies the display will continue to show whatever is currently being displayed for normal operation (blinking decimal, active error code, heat state, etc..)

** After the art flashing the

0

seconds. If push button is pressed again and held during that time, the control will start to display characters corresponding

to different variable speed furnace models for 3 seconds each. While the wanted character−model is displayed push button has to be released. Selected option will flash display for 10 seconds and during that time push button has to be pressed

and held for 5 seconds. Once control accepts new setting it will store data in non−volatile memory and reset itself. If 10 sec-

onds expires or push button is held less than 5 seconds, control will exit filed test mode and go in idle without programming

the unit size.

Integrated Control Diagnostic Codes

Press the diagnostic push button and hold it to cycle through a menu of options. Every five seconds a new menu item will be

displayed. Release the button when the desired mode is displayed.

 

 

 

 

 

When a solid "P" is displayed, the furnace capacity / size is programmed.

 

 

 

 

 

When the solid

 

 

 

 

 

options: No change (displaying error history) remains in Diagnostic Recall mode; solid

 

" exits Diagnostic Recall mode;

and solid . Must press button while flashing

 

 

 

 

 

When the solid

 

 

 

 

 

cycle/reset, by pressing and holding the push button until 3 horizontal line are displayed

 

 

ter 10 minutes of entering

flame signal mode.

 

 

 

 

 

 

 

 

Code

Diagnostic Codes/Status of Equipment

Action Required to Clear and Recover

 

 

 

 

 

 

 

.

Idle mode (Decimal blinks at 1 Hertz −− 0.5 second ON, 0.5 second OFF).

 

 

 

 

 

 

 

 

 

 

 

 

A

Cubic feet per minute (cfm) setting for indoor blower (1 second ON, 0.5

 

 

 

 

 

 

second OFF) / cfm setting for current mode displayed.

 

 

 

 

 

 

 

 

 

 

 

 

C

Cooling stage (1 second ON, 0.5 second OFF) / 1 or 2 displayed / Pause

 

 

 

 

 

 

/ cfm setting displayed / Pause / Repeat codes).

 

 

 

 

 

 

 

 

 

 

 

 

d

Dehumidification mode (1 second ON) / 1 second OFF) / cfm setting dis-

 

 

 

 

 

 

played / Pause / Repeat Codes).

 

 

 

 

 

 

 

 

 

 

 

 

h

Heat pump stage (1 second ON, 0.5 second OFF) / % of input rate dis-

 

 

 

 

 

 

played / Pause / cfm setting / Pause / Repeat codes.

 

 

 

 

 

 

 

 

 

 

 

 

H

Gas Heat Stage (1 second ON, 0.5 second OFF) / 1 or 2 displayed /

 

 

 

 

 

 

Pause / cfm

 

 

 

 

 

 

setting displayed / Pause / Repeat codes. Blinking during ignition.

 

 

 

 

 

 

 

 

 

 

 

 

dF

Defrost mode.

 

 

 

 

 

 

 

 

 

 

 

 

U

Discharge Air Temperature

 

 

 

 

 

 

 

 

 

 

 

 

Page 60

Page 60
Image 60
Lennox International Inc SL280UH090V48B Integrated Control Diagnostic Modes, Integrated Control Diagnostic Codes