Lochinvar WH 55-399 Sidewall direct venting continued, 2A Clearance to Gravity Air Inlets

Models: WH 55-399

1 80
Download 80 pages 39.75 Kb
Page 23
Image 23
4 Sidewall direct venting (continued)

Installation & Operation Manual

4 Sidewall direct venting (continued)

Vent/air termination – sidewall

Figure 4-1CAlternate PVC/CPVC/SS/ Polypropylene Venting Arrangement (if Space Allows) w/Field Supplied Fittings

TO BOILER

INTAKE AIRCOUPLING

CONNECTION

12” MIN

15” MAX

FROM BOILER

VENT PIPE

CONNECTION

BIRD SCREEN

12”

MIN

BIRD

SCREEN

GRADE OR

SNOW LINE

ALTERNATE VENTING ARRANGEMENT

(IF SPACE PERMITS)

Figure 4-1DAlternate SS Venting Arrangement - Typical Stainless Steel Sidewall Termination of Air and Vent w/Field Supplied Fittings, Utilizing a Hood Intake

6.Locate terminations so they are not likely to be damaged by foreign objects, such as stones or balls, or subject to buildup of leaves or sediment.

Figure 4-2AClearance to Gravity Air Inlets

12"

MIN.

VENT / AIR

TERMINATION

12" Figure 4-2AClearance to Gravity Air InletsMIN.

12" Figure 4-3AClearance to Forced Air InletsMIN.

BIRD SCREEN

TO BOILER

INTAKE AIR

Manual backgroundCONNECTION

12" (305 MM) MIN 15" (381 MM) MAX

FROM BOILER

VENT PIPE

CONNECTION

12" (305 MM) MIN

GRADE OR

SNOW LINE

5.Maintain clearances as shown in FIG.’s 4-1A thru 4-3B, pages 22 - 24. Also maintain the following:

a.Vent must terminate:

At least 6 feet from adjacent walls.

No closer than 12 inches below roof overhang.

At least 7 feet above any public walkway.

At least 3 feet above any forced air intake within 10 feet.

No closer than 12 inches below or horizontally from any door or window or any other gravity air inlet.

b.Air inlet must terminate at least 12 inches above grade or snow line; at least 12 inches below the vent termination; and the vent pipe must not extend more than 24 inches vertically outside the building as shown in FIG. 4-1B. Condensate could freeze and block vent pipe.

c.Do not terminate closer than 4 feet horizontally from any electric meter, gas meter, regulator, relief valve, or other equipment. Never terminate above or below any of these within 4 feet horizontally.

Figure 4-2BAlternate Clearance to Gravity Air Inlets w/ Field Supplied Fittings

12”

MIN.

BIRD

SCREEN

(TYPICAL)

12” Manual backgroundMIN.

12” Manual backgroundMIN.

Figure 4-3AClearance to Forced Air Inlets

IF LESS

THAN 10’

VENT / AIR

36"

TERMINATION

MIN.

 

FORCED AIR

INLET

7' MIN. ABOVE ANY PUBLIC WALKWAY

Manual background 23 Manual background

Page 23
Image 23