Lochinvar WH 55-399 Number of Units, Required Pipe Sizes, Model, Hydronic piping continued

Models: WH 55-399

1 80
Download 80 pages 39.75 Kb
Page 41
Image 41
Number of Units

Installation & Operation Manual

6 Hydronic piping (continued)

Figure 6-6Multiple Boilers - Single Temperature Zoned with Zone Valves - DHW Priority

 

 

 

Number of Units

 

Model

2

3

4

5

6

7

8

 

 

Required Pipe Sizes

 

55

1-1/4"

1-1/2"

1-1/2"

2"

2"

2"

2"

85

1-1/4"

1-1/2"

2"

2"

2"

2-1/2"

2-1/2"

110

1-1/2"

2"

2"

2-1/2"

2-1/2"

2-1/2"

3"

155

2"

2"

2-1/2"

2-1/2"

3"

3"

4"

199

2"

2"

2-1/2"

3"

4"

4"

4"

285

2-1/2"

2-1/2"

3"

4"

4"

4"

5"

399

2-1/2"

3"

4"

4"

5"

5"

5"

 

 

ZONE #1

 

PRESSURE

 

BACKFLOW

REDUCING

ZONE #2 ZONE #3 ZONE #4

PREVENTER

VALVE

PRESSURE

BALL VALVE

 

GAUGE

 

ZONE VALVES

(TYPICAL)

 

(TYPICAL)

 

MAKE UP WATER

 

 

SYSTEM SUPPLY

DIFFERENTIAL PRESSURE

 

BYPASS VALVE

 

SENSOR

(RECOMMENDED)

AIR SEPARATOR

 

 

 

SYSTEM

EXPANSION

CIRCULATOR

 

TANK

 

DRAIN POINT

(TYPICAL)

BOILER

CIRCULATOR

PRESSURE

RELIEF VALVE

ModelRequired Pipe Sizes MAY SUBSTITUTE LOW LOSS HEADER

NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART

Y-STRAINER

ANTI-SCALD

 

MIXING VALVE

 

(RECOMMENDED)

 

HOT

(TYPICAL)

DOMESTIC

 

WATER

 

HOT WATER

OUT

 

CIRCULATOR

 

Manual backgroundManual backgroundManual backgroundManual backgroundManual background COLD

WATER

IN

BOILER 2

(MEMBER 1)

BOILER 1 (LEADER)

INDIRECT

DHW TANK

TEMPERATURE /

 

 

 

DRAIN

 

 

 

 

 

 

UNION

PRESSURE

 

 

 

GAUGE

 

 

 

(TYPICAL)

NOTICE

Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.

Manual background 41 Manual background

Page 41
Image 41
Lochinvar WH 55-399 operation manual Number of Units, Required Pipe Sizes, Model, Hydronic piping continued, Notice