Lochinvar WH 55-399 Sidewall direct venting continued, Installation & Operation Manual, Notice

Models: WH 55-399

1 80
Download 80 pages 39.75 Kb
Page 27
Image 27
Manual background

Installation & Operation Manual

4 Sidewall direct venting (continued)

Sidewall termination – optional concentric vent models

Figure 4-92" and 3" Concentric Vent Dimensional Drawing (reference Table 3D on page 19)

Figure 4-104" Concentric Vent Dimensional Drawing (reference Table 3D on page 19)

Manual backgroundManual background "B" DIA. "C" DIA.

Manual background 3" (76 MM)

"G"

"B" DIA. PVC VENT / EXHAUST

"D"

"H" DIA.

"E"

"F"

A

B

C

D

E

F

G

H

60"

4"

6"

21 1/8"

10"

7 5/8"

3"

6 5/8"

(1524 MM)

(102 MM)

(152 MM)

(537 MM)

(254 MM)

(194 MM)

(76 MM)

(168 MM)

 

 

 

 

 

 

 

 

NOTICE

Instead of cementing the smaller pipe to

the rain cap, a field-supplied stainless steel

 

screw may be used to secure the two (2)

 

components together when field disassembly

 

is desired for cleaning (see FIG. 4-11).

5.Install the Y concentric fitting and pipe assembly through the structure’s hole.

NOTICE

Do not allow insulation or other materials

to accumulate inside the pipe assembly

 

 

when installing through the hole.

￿WARNING

￿WARNING

When using the alternate screw assembly method, drill a clearance hole in the rain cap and a pilot hole in the vent pipe for the screw size being used. Failure to drill adequate holes may cause cracking of PVC components, allowing combustion products to be recirculated. Failure to follow this warning could result in personal injury or death.

Do not operate the appliance with the rain cap removed or recirculation of combustion products may occur. Water may also collect inside the larger combustion air pipe and flow to the burner enclosure. Failure to follow this warning could result in product damage or improper operation, personal injury, or death.

6.Install the rain cap and small diameter pipe assembly into the Y concentric fitting and large pipe assembly. Ensure small diameter pipe is bottomed and cemented in the Y concentric fitting for #CVK3003 and 3008 installations and fastened tightly into the rubber adapter for #CVK3007 installations.

7.Secure the assembly to the structure as shown in FIG. 4-12 using field-supplied metal strapping or equivalent support material.

NOTICE

Ensure termination location clearance

dimensions are as shown in FIG. 4-6.

 

If assembly needs to be extended to allow

NOTICE

sidewall thickness requirement, the two (2)

 

 

pipes supplied in the kit may be replaced

 

by using the same diameter, field-supplied

 

SDR-26 PVC (D2241) pipe for CVK3003

 

and 3008, and standard schedule 40 PVC

Figure 4-11Rain Cap to Vent Pipe Alternate Assembly

 

for CVK3007. Do not extend dimension

 

D more than 60 inches (see FIG. 4-9 and

 

FIG. 4-10).

 

If assembly needs to be reduced, dimension

NOTICE

D can be as short as possible.

 

Manual background 27 Manual background

Page 27
Image 27
Lochinvar WH 55-399 operation manual Sidewall direct venting continued, Installation & Operation Manual, Notice