Installation & Operation Manual
6 Hydronic piping
Figure
|
|
| Number of Units |
| |||
Model | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
|
| Required Pipe Sizes |
| ||||
55 | 2" | 2" | 2" | 2" | |||
85 | 2" | 2" | 2" | ||||
110 | 2" | 2" | 3" | ||||
155 | 2" | 2" | 3" | 3" | 4" | ||
199 | 2" | 2" | 3" | 4" | 4" | 4" | |
285 | 3" | 4" | 4" | 4" | 5" | ||
399 | 3" | 4" | 4" | 5" | 5" | 5" |
| PRESSURE | TEMPERATURE | TEMPERATURE | TEMPERATURE | WIRES TO |
BACKFLOW | REDUCING VALVE | LOOP #1 | LOOP #2 | LOOP #3 | LOOP |
PREVENTER | PRESSURE |
|
|
| SENSORS |
|
|
|
|
| |
| GAUGE |
|
|
|
|
MAKE |
|
UP | MIXING VALVES |
WATER | (TYPICAL) |
| SYSTEM |
| SUPPLY |
| SENSOR |
| AIR SEPARATOR |
| EXPANSION |
| TANK |
| MAY SUBSTITUTE |
| LOW LOSS HEADER |
BALL VALVE |
(TYPICAL) |
DRAIN POINT
(TYPICAL)
BOILER
CIRCULATOR
NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART
| 24V SIGNAL TO |
| |
| MIXING VALVES |
| |
120VAC TO PUMPS |
| ||
DOMESTIC |
| ||
LOOP CONTROL |
| ||
HOT WATER |
|
| |
CIRCULATOR |
|
| |
FLOW | SHIELDED CABLE TO |
| |
BOILER CONTROL |
| ||
CHECK |
| ||
HOT WATER | |||
VALVE | |||
| OUT | MIXING VALVE | |
|
| COLD | |
|
| WATER | |
|
| IN |
PRESSURE
RELIEF
VALVE
BOILER | BOILER |
CAUTION
NOTICE
NOTICE
| DRAIN | INDIRECT | ||
UNION |
|
| TEMPERATURE / | DHW TANK |
|
| |||
(TYPICAL) |
|
| PRESSURE GAUGE |
|
|
|
| IMG00191 | |
|
|
|
|
Mixing valves are required for the protection of low temperature loops.
Please note that the installer is responsible for ensuring DHW prioritization when piped as a zone.
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
44