ZONE #1

Installation & Operation Manual

6 Hydronic piping (continued)

Figure 6-4Single Boiler - Single Temperature with Zone Valves - DHW Priority

 

ZONE #1

 

PRESSURE

PRESSURE

 

REDUCING VALVE

GAUGE

ZONE #3

 

ZONE #2

BACKFLOW

 

 

PREVENTER

 

 

MAKE UP

 

 

WATER

 

 

SYSTEM SUPPLY SENSOR

 

AIR SEPARATOR

 

 

 

SYSTEM

 

 

CIRCULATOR

 

 

EXPANSION

 

 

TANK

 

ZONE #4

ZONE VALVES (TYPICAL)

DIFFERENTIAL PRESSURE BYPASS VALVE (RECOMMENDED)

 

MAY SUBSTITUTE LOW LOSS HEADER

 

BALL VALVE

NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART

 

 

 

 

(TYPICAL)

 

 

 

 

Y-STRAINER

 

HOT

 

 

WATER

 

(RECOMMENDED)

 

 

 

OUT

 

 

 

DRAIN POINT

FLOW CHECK

DOMESTIC

ANTI-SCALD

(TYPICAL)

VALVE

HOT WATER

MIXING VALVE

 

 

CIRCULATOR

 

 

 

 

COLD

BOILER

 

 

WATER

CIRCULATOR

 

 

IN

 

PRESSURE

 

 

 

RELIEF VALVE

 

 

BOILER

UNION ZONE #3

(TYPICAL)DRAIN

TEMPERATURE /

PRESSURE

GAUGE

NOTICE

Please note that these illustrations are meant to show system piping concept only, the installer is responsible

for all equipment and detailing required by local codes.

39

 