6 Hydronic piping

Figure 6-7Multiple Boilers - Single Temperature Zoned with Circulators - DHW Priority

 

 

 

Number of Units

 

Model

2

3

4

5

6

7

8

 

 

Required Pipe Sizes

 

55

1-1/4"

1-1/2"

1-1/2"

2"

2"

2"

2"

85

1-1/4"

1-1/2"

2"

2"

2"

2-1/2"

2-1/2"

110

1-1/2"

2"

2"

2-1/2"

2-1/2"

2-1/2"

3"

155

2"

2"

2-1/2"

2-1/2"

3"

3"

4"

199

2"

2"

2-1/2"

3"

4"

4"

4"

285

2-1/2"

2-1/2"

3"

4"

4"

4"

5"

399

2-1/2"

3"

4"

4"

5"

5"

5"

 

 

ZONE #1

 

 

PRESSURE

 

 

 

 

REDUCING VALVE

PRESSURE

ZONE #2 ZONE #3 ZONE #4

 

BACKFLOW

GAUGE

 

 

 

 

PREVENTER

 

 

 

 

MAKE UP

 

 

 

FLOW CHECK

WATER

 

 

 

 

 

 

VALVE

SYSTEM SUPPLY

 

 

 

(TYPICAL)

SENSOR

 

 

 

 

AIR SEPARATOR

 

 

 

ZONE CIRCULATORS

 

 

 

 

(TYPICAL)

 

EXPANSION

 

 

 

 

TANK

 

 

BALL VALVE

 

MAY SUBSTITUTE LOW LOSS HEADER

 

(TYPICAL)

 

NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART

DRAIN POINT

 

 

 

 

 

(TYPICAL)

 

 

ANTI-SCALD

 

 

 

 

HOT

 

 

Y-STRAINER

MIXING VALVE

 

 

 

WATER

 

 

(RECOMMENDED)

 

 

 

 

OUT

 

 

(TYPICAL)

DOMESTIC

 

 

 

 

 

 

HOT WATER

 

BOILER

 

CIRCULATOR

COLD

CIRCULATOR

 

 

WATER

 

PRESSURE

 

 

IN

RELIEF VALVE

 

 

 

BOILER 2

BOILER 1

(MEMBER 1)

(LEADER)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INDIRECT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRAIN

 

 

TEMPERATURE /

 

 

 

 

 

 

DHW TANK

 

 

 

 

 

UNION

 

 

 

 

 

 

PRESSURE

 

 

 

 

(TYPICAL)

 

 

 

 

 

GAUGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 