5 Vertical direct venting

Vent/air termination – vertical

￿WARNING Follow instructions below when determining vent location to avoid

possibility of severe personal injury, death or substantial property damage.

Installation & Operation Manual

Figure 5-1APVC/CPVC/Polypropylene Vertical Termination of Air and Vent

ALTERNATE INTAKE LOCATIONS:

INTAKE PIPES MAY BE LOCATED

ANYWHERE WITHIN 24” OF VENT

PIPE

Determine location

Locate the vent/air terminations using the following guidelines:

1.

The total length of piping for vent or air must not exceed

 

the limits given in the General Venting Section on page

 

16 of this manual.

2.

Prepare the vent termination and the air termination

 

elbow (FIG. 5-1A) by inserting bird screens. Bird screens

 

should be obtained locally.

3.

The vent must terminate at least 3 feet above the highest

 

place in which the vent penetrates the roof and at least

 

2 feet above any part of a building within 10 horizontal

BIRD SCREEN (TYPICAL)

COUPLING (FIELD SUPPLIED)

VENT OUTLET

12” MINIMUM ABOVE AIR INLET

VENT

6” MINIMUM ABOVE ROOF / SNOW LINE

COMBUSTION

AIR

feet.

4. The air piping must terminate in a down-turned 180°

return pipe no further than 2 feet from the center of the

Figure 5-1BStainless Steel Vertical Termination of Air and Vent

vent pipe. This placement avoids recirculation of flue

products into the combustion air stream.

5. The vent piping must terminate in an up-turned coupling

as shown in FIG. 5-1A. The top of the coupling must

be at least 1 foot above the air intake. When the vent

termination uses a rain cap as illustrated in FIG. 5-1B

maintain at least 36" (914 mm) above the air inlet. The

air inlet pipe and vent pipe can be located in any desired

position on the roof, but must always be no further than

ALTERNATE INTAKE LOCATIONS: INTAKE PIPES MAY BE LOCATED ANYWHERE WITHIN 24” (610 MM)

OF VENT PIPE

VENT

BIRD SCREEN

(TYPICAL)

2 feet (.6 m) apart and with the vent termination at least

1 foot for PVC and 3 feet for stainless steel, above the air

intake.

6. Maintain the required dimensions of the finished

termination piping as shown in FIG. 5-1A.

7. Do not extend exposed vent pipe outside of building

more than shown in this document. Condensate could

freeze and block vent pipe.

￿ WARNING Rooftop vent and air inlet terminations

must terminate in the same pressure

zone, unless vertical vent sidewall air is set up as shown in the General Venting - Vertical Vent, Sidewall Air Section.

6" (152 MM) MINIMUM

ABOVE ROOF /

SNOW LINE

COM,BUSTION

AIR

VENT OUTLET

36” (914 MM) MINIMUM

ABOVE AIR INLET

8.Locate terminations so they are not likely to be damaged by foreign objects or subject to buildup of leaves or sediment.

Prepare roof penetrations

1.Air pipe penetration:

a.Cut a hole for the air pipe. Size the air pipe hole as close as desired to the air pipe outside diameter.

2.Vent pipe penetration:

a.Cut a hole for the vent pipe. For either combustible or noncombustible construction, size the vent pipe hole with at least a 1/2 inch clearance around the vent pipe outer diameter:

3½ inch hole for 2 inch vent pipe

4½ inch hole for 3 inch vent pipe

b.Insert a galvanized metal thimble in the vent pipe hole.

29

Page 29
Image 29
Lochinvar WH 55-399 operation manual Vertical direct venting, Vent/air termination vertical, Prepare roof penetrations

WH 55-399 specifications

The Lochinvar WH 55-399 is a high-efficiency water heater designed for residential and commercial applications, offering a reliable solution for hot water needs. This model represents an advanced approach to water heating, combining cutting-edge technologies and features that ensure optimal performance and energy efficiency.

One of the standout features of the Lochinvar WH 55-399 is its high thermal efficiency, which is a key factor in reducing energy consumption and operating costs. With an efficiency rating exceeding 90%, this water heater ensures that more energy is converted into usable hot water, making it an environmentally friendly choice.

The WH 55-399 utilizes advanced condensing technology, which allows it to extract additional heat from the exhaust gases before they are expelled. This process not only increases efficiency but also significantly decreases greenhouse gas emissions. The unit is also equipped with an intelligent control system that allows for precise temperature adjustments, ensuring that the user has an optimal supply of hot water while maintaining energy savings.

Another important aspect of this model is its impressive recovery rate. The ability to quickly heat water after a significant draw ensures that users will not experience interruptions in their hot water supply, making it ideal for busy households or commercial environments. This is particularly beneficial in applications requiring consistent hot water availability, such as restaurants or athletic facilities.

The Lochinvar WH 55-399 is designed with durability in mind. Constructed from high-quality materials, this water heater boasts a robust tank lined with corrosion-resistant coatings, extending the lifespan of the unit and reducing maintenance needs. Additionally, it features a reliable gas burner and a well-insulated tank, contributing to its overall efficiency and performance.

Safety is also a priority with the WH 55-399. The unit incorporates multiple safety features, including a flame sensor, automatic shut-off valve, and over-temperature protection, ensuring peace of mind for users.

In summary, the Lochinvar WH 55-399 stands out with its combination of high efficiency, advanced technology, and durable construction. Whether for residential or commercial use, this water heater provides a dependable and cost-effective solution for all hot water needs. Its innovative design and performance characteristics make it a top choice for anyone seeking a premium water heating option.