7 Gas connections (continued)

7 Gas connections (continued)

Installation & Operation Manual

￿WARNING

￿WARNING

Failure to apply pipe sealing compound as detailed in this manual can result in severe personal injury, death, or substantial property damage.

Knight wall mount boilers are typically shipped ready to fire on natural gas. Check boiler rating plate to determine which fuel the boiler is set for. If set to natural gas, it may be converted to LP by installing an orifice (see page 13). In order to operate on LP gas, an orifice MUST BE installed. Failure to comply could result in severe personal injury, death, or substantial property damage.

Natural gas:

Pipe sizing for natural gas

1.Refer to Table 7A for pipe length and diameter. Based on rated boiler input (divide by 1,000 to obtain cubic feet per hour).

a.Table 7A is only for natural gas with specific gravity 0.60 inches, with a pressure drop through the gas piping of 0.5 inches w.c.

b.For additional gas pipe sizing information, refer to ANSI Z223.1 (or B149.1 for Canadian installations).

Natural gas supply pressure requirements

￿WARNING

Use two wrenches when tightening gas piping at boiler (FIG. 7-2), using one wrench to prevent the boiler gas line connection from turning. Failure to support the boiler gas connection pipe to prevent it from turning could damage gas line components.

1.Pressure required at the gas valve inlet pressure port:

Maximum 14 inches w.c. with no flow (lockup) or with boiler on.

Minimum 4 inches w.c. with gas flowing (verify during boiler startup).

2.Install 100% lockup gas pressure regulator in supply line if inlet pressure can exceed 14 inches w.c. at any time. Adjust lockup regulator for 14 inches w.c. maximum.

Figure 7-2Inlet Pipe with Backup Wrench

Propane Gas:

￿WARNING

Knight wall mount boilers are typically shipped ready to fire on natural gas. Check boiler rating plate to determine which fuel the boiler is set for. If set to natural gas, it may be converted to LP by installing an orifice (see page 13). In order to operate on LP gas, an orifice MUST BE installed. Failure to comply could result in severe personal injury, death, or substantial property damage.

 

USE BACK UP WRENCH

 

 

 

 

 

TO PREVENT PIPE FROM

 

ROTATING

 

Maximum inlet gas pressure must not

NOTICE

 

exceed the value specified. Minimum

 

 

value listed is for the purposes of input

 

adjustment.

Pipe sizing for propane gas

1.Contact gas supplier to size pipes, tanks, and 100% lockup gas pressure regulator.

Propane Supply Pressure Requirements

1.Adjust propane supply regulator provided by the gas supplier for 14 inches w.c. maximum pressure.

2.Pressure required at gas valve inlet pressure port:

Maximum 14 inches w.c. with no flow (lockup) or with boiler on.

Minimum 8 inches w.c. with gas flowing (verify during boiler startup).

￿ WARNING Ensure that the high gas pressure regulator is at least 6 - 10 feet upstream of the

appliance.

Natural gas: 49 Pipe sizing for natural gas