Researching the requirements
31
Notes for Figure 4:
-
An isolated ground receptacle must be used for systems with isolated
ground.
An isloated ground receptacle with individual hot neutral and ground
conductors must be used for systems with isolated ground.
An alternate earthing electrode, if required, must be installed in a
minimum of 6 ft. (1.8m) from the building earth reference.
Connections to the building earth reference must be either cadwelded or
provided with two ALCU clamps.
NEMA numbers for IG ground receptacles are:
208/240
@
30
A IG-L6-30
120 @
15 A IG-5-15
Panel circuit breakers are:
. .
208Vl24OV 30A
Connection of the LRE to the building ground source should be made at
the same physical location as the transformer grounding conductor. If
the LRE is connected to a building ground point other than the
transformer ground point, a bonding jumper must be installed between
the two points.
Installation planning
. .
553-3001-l 20