Epilson STSTM
Step 2 Connection of Utility Power InputsConnect Input Power from Two Sources
The Epsilon STS™ systems provides for either top or bottom cable entry. Connections are to be made with 75°C copper wire cables and using the lugs supplied with the STS unit. Refer to section 2.0 Installation and/or the system installation drawing(s) for more details (such as cable size and number of conductors).
NOTE: Three phase input power supplied as a Wye must have a separate, solidly grounded neutral that will be connected to the STS neutral busbar. If neutral is not supplied or not required for the load, connect only three phases and ground.
It is recommended to use isolation transformers so that the neutral of both AC sources can be grounded to the same potential.
Step 3 Connection of the Load OutputsThe Epsilon STS™ system provides for either top or bottom cable entry. Connections are to be made with 75°C copper wire cables and using the lugs supplied with the STS unit. Refer to section 2.0 Installation and/or the system installation drawing(s) for more details (such as cable size and number of conductors).
NOTE: Input and output cables inside the STS cabinet must be braced at 12” intervals as shown in Figures
For Control Wiring connections refer to section 2.0 Installation.
Figure
CONTROL WIRES
THREADED THROUGH
TOP ENTRY
CONDUIT PLATECONTROL WIRE
TB1
TERMINAL
CONTROL
WIRES
COMMUNICATION
CARDS
BRACE AT 12" INTERVALS
BOTTOM ENTRY
CONDUIT PLATE