Epilson STSTM
1.7.4Accessing Electrical Connections
CAUTION: Only an authorized electrical professional should access electrical con- nections. A severe shock hazard exists.
The ONLY user serviceable items in the Epsilon STS™ unit are:
A.The input power connections
B.The load connection
C.Any wire connections to the customer control terminal block.
D.The communication card options
The access method for connections made to the communication cards is clearly seen when the front door to the Epsilon STS™ unit is opened. Figure
Figure
CONTROL WIRES
THREADED THROUGH
TOP ENTRY
CONDUIT PLATECONTROL WIRE
TB1
TERMINAL
CONTROL
WIRES
COMMUNICATION
CARDS
BRACE AT 12" INTERVALS
BOTTOM ENTRY
CONDUIT PLATE
Table
# OF CABLES PER |
| MINIMUM | CABLE LUG | CONDUIT | ||
|
|
|
| CABLE SIZE | (SUPPLIED) | HOLE |
|
|
|
| |||
PHASE | N |
| GND | (75°C, CU) |
| DIA. (QTY.) |
1 | 2 |
| 1 | # 4/0 AWG | # 4/0, 3/8” STUD | |
|
|
|
|
| (T&B L973 OR EQUIV.) |
|
1 — 10 | Introduction |