Installation and User Manual

Figure 1-6: 400/600 STS Power and Control Wire Connections.

CONTROL WIRE PANDUIT/WIRE-WAYS

TOP ENTRY CONDUIT PLATE

COMMUNICATION

 

CARDS

 

TB1

CONTROL WIRES

THREADED THROUGH

TERMINAL

UNIT.

 

CONTROL WIRE

PANDUIT/WIRE-WAYS

BRACE AT

12" INTERVALS

CONTROL WIRES

BOTTOM ENTRY

CONDUIT PAN

Table 1-2: Input/Output Power Connections.

STS

# OF CABLES PER

 

MINIMUM

CABLE LUG

CONDUIT

 

RATING

PHASE

N

GND

 

CABLE SIZE

(SUPPLIED)

HOLE

(AMPS)

 

 

 

 

(75°C, CU)

 

DIA.

(QTY.)

 

 

 

 

 

 

 

 

 

400

2

4

1

 

# 250 MCM

# 250 MCM, 3/8” STUD

4”

(3)

 

 

 

 

 

 

(T&B M973 OR EQUIV.)

 

 

600

3

5

1

 

# 250 MCM

# 250 MCM, 3/8” STUD

4-1/2” (3)

 

 

 

 

 

 

(T&B M973 OR EQUIV.)

 

 

86-504004-00 B03

Introduction

1 — 11