Installation and User Manual

2.5Setting the Output Relay Contacts and Input Switching States

Set DIP switch SA2 for one of the following configuration modes:

N.O. Setting (default) All switches OFF

SA1

8

1

ON OFF

N.C. Setting

All switches ON

SA2

8

N.C. N.O.

1

ON OFF

NOTE:

By default, all the relay contacts are Normally Open (NO) (see section 1.4):

Contact open = relay not controlled.

Contact closed = relay controlled.

By default, the inputs are activated when the external contact is closed (NO):

External contact open = input not activated.

External contact closed = input activated.

It is possible to individually set each relay and input to N.O. or N.C. mode by setting each switch on SA2 individu- ally. The parameters for relays 1 to 6 are set using SA2 DIP switches 1 to 6 respectively. The parameters for inputs A and B are set using SA2 DIP switches 7 and 8 respectively.

When the SA2 DIP switch is set to OFF, the relay/input is set to N.O.

When the SA2 DIP switch is set to ON, the relay/input is set to N.C.

86-504004-00 B03

Installation

2 — 9