Installation and User Manual
2.5Setting the Output Relay Contacts and Input Switching States
Set DIP switch SA2 for one of the following configuration modes:
N.O. Setting (default) All switches OFF
SA1
8
1
ON OFF
N.C. Setting
All switches ON
SA2
8
N.C. N.O.
1
ON OFF
NOTE:
By default, all the relay contacts are Normally Open (NO) (see section 1.4):
◗Contact open = relay not controlled.
◗Contact closed = relay controlled.
By default, the inputs are activated when the external contact is closed (NO):
◗External contact open = input not activated.
◗External contact closed = input activated.
It is possible to individually set each relay and input to N.O. or N.C. mode by setting each switch on SA2 individu- ally. The parameters for relays 1 to 6 are set using SA2 DIP switches 1 to 6 respectively. The parameters for inputs A and B are set using SA2 DIP switches 7 and 8 respectively.
When the SA2 DIP switch is set to OFF, the relay/input is set to N.O.
When the SA2 DIP switch is set to ON, the relay/input is set to N.C.