Installation and User Manual
2.3.5Connection of the Relay Communication Card
The relay communications card contains six programmable dry contact outputs and two programmable dry contact inputs, and is standard on the Epsilon STS™. The inputs and outputs are factory programmed according to functions listed in Table
Table
| Inputs | Factory Setting | Options (available on both contacts) | ||
|
|
|
|
| - Reset Memorized Faults. |
1.A |
| - Select Source S1 as Preferred. | - Select Source S1as Preferred. | ||
| |||||
|
|
|
|
| - Select Source S2 as Preferred. |
|
|
|
|
| - Enable Automatic Retransfer. |
1.B |
|
|
| - Select Source S2 as Preferred. | - Disable Automatic Retransfer. |
|
|
| |||
|
|
|
|
| - Enable Transfers. |
|
|
|
|
| - Disable Transfers. |
Note: 1. Power sources connected to card must be equipped with protection devices with a maximum breaking capacity of 2A.
2.Connections must be form “C” Dry Contacts.
Outputs | Factory Setting | Options (available on all contacts) | ||||
1.1 |
|
|
|
| - Power supplied to Load. | - Power supplied to Load. |
|
|
|
| |||
|
|
|
| |||
|
|
|
|
|
| - Summary Alarm (source or STS fault). |
1.2 |
|
|
|
| - Summary Alarm | - STS Fault. |
|
|
|
| |||
|
|
|
| |||
|
|
|
|
| (source or STS fault). | - Source S1 |
1.3 |
|
|
|
| - STS Fault. | - Source S2 |
|
|
|
| |||
|
|
|
| |||
|
|
|
|
|
| - Sources |
1.4 |
|
|
|
| - Overload Condition. | - Source S1 Active. |
|
|
|
| |||
|
|
|
| |||
|
|
|
|
|
| - Source S2 Active. |
1.5 |
|
|
|
| - Source S1 | - Source S1 is Preferred Source. |
|
|
|
| |||
|
|
|
| |||
|
|
|
|
| - Automatic Transfer Disabled. | |
1.6 |
|
|
|
| - Source S2 | - Overload Condition. |
|
|
|
| |||
|
|
|
| |||
|
|
|
|
|
|
The indications 1.X become 2.X for a second optional card of the same type.
Installation | 2 — 5 |