Installation and User Manual

2.2.1Conduit Plate Location (bottom entry)

Cable entry through the bottom is the standard preferred design for the Epsilon STS™ cabinet. Please see the following figure for the location of the bottom entry conduit plate.

Figure 2-2: 200A /400/600A STS Cabinet Footprint and Top View.

200A STS

 

REMOVABLE

REMOVABLE

 

CONDUIT PAN

CONDUIT PLATE

 

10.0 X 7.0 OPENING

8.3 X 8.3 OPENING

 

CASTERS

 

 

(4 PLACES)

 

 

LEVELING JACKS

 

FOOTPRINT

(4 PLACES)

TOP VIEW

400/600A STS

LEVELING JACKS

CASTERS

REMOVABLE

REMOVABLE

 

 

CONDUIT PAN

CONDUIT PLATE

 

 

12.4 X 16.5 OPENING

20.6 X 7.3 OPENING

 

FOOTPRINT

 

TOP VIEW

2.3Source #1 AC Input Connections

The connections to be made are the three phases, neutral (if used) and ground cables of input AC Source #1 to the STS. The main 3-phase cables of input Source #1 are terminated at the Source #1 input busbars. Neutral (if supplied) and Ground cables are terminated at the Neutral (N) and Ground (GND) busbars respectively. All cables from Source #1 should be run in a single conduit separately from all other cables (power supply or computer-system interconnection cables). They should not pass near interference-emitting equipment or sensitive loads. Complete wiring instructions for your installation are provided on the installation drawings supplied with the equipment. See Figure 1-5 and 1-6, refer to table 1-1 and 1-2 for details.

2.3.1.Source #2 AC Input Connections

The connections to be made are the three phases, neutral (if used) and ground cables of input AC Source #2 to the STS. The main 3-phase cables of input Source #2 are terminated at the Source #2 input busbars. Neutral (if supplied) and Ground cables are terminated at the Neutral (N) and Ground (GND) busbars respectively. All cables from Source #2 should be run in a single conduit separately from all other cables (power supply or computer-system interconnection cables). They should not pass near interference-emitting equipment or sensitive loads. Complete wiring instructions for your installation are provided on the installation drawings supplied with the equipment. See Figure 1-5 and 1-6, refer to table 1-1 and 1-2 for details.

2.3.2AC Output Connections

The connections to be made are the three phases, neutral(if used) and ground cables from the load to the STS. The main 3-phase cables from the load are terminated at the Output busbars. Neutral(if supplied) and Ground cables are terminated at the Neutral(N) and Ground(GND) busbars respectively. All cables from the load should be run in a single conduit separately from all other cables(power supply or computer-system interconnection cables).

86-504004-00 B03

Installation

2 — 3