Installation and User Manual

3.15Epsilon STS™ Customization

Certain parameters can be customized as follows:

1.Press the <Menu> button.

2. Select <Setup>, then <Customization> using the function buttons marked

or

.

3.Confirm by pressing the function button marked ￿

4.Enter the password (default factory password is “0 0 0”. Select Setup, then Password to change the password).

Figure 3-6: Customization Screen.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Customization active

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal Voltage

480V

 

 

 

 

 

 

 

 

 

Overvoltage threshold

10%

 

 

 

 

 

 

 

 

 

 

 

Undervoltage threshold

10%

 

 

 

 

 

 

 

 

 

 

 

Nominal frequency

60 Hz

 

 

 

 

 

 

 

 

 

Over-frequency threshold

5%

 

 

ES

 

 

 

 

Under-frequency threshold

5%

 

 

 

 

 

 

 

 

 

C

 

 

 

 

Phase error tolerance S1/S2

15°

 

 

 

 

 

 

 

 

 

 

 

Retransfer

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 3-1: Customization Settings.

Parameter

Factory setting

Customization

Nominal Voltage (both sources)

As specified by customer

208,220,240,440,480,575,600V

 

 

 

Overvoltage threshold

+10%

+5% to +20% (1% steps)

 

 

 

Undervoltage threshold

-10%

-5% to –20% (1% steps)

 

 

 

Nominal Frequency (both sources)

60 Hz

50 or 60 Hz

 

 

 

Over-frequency threshold

+5%

+1 to +10% (0.5% steps)

 

 

 

Under-frequency threshold

-5%

-1 to -10% (0.5% steps)

 

 

 

Phase error tolerance (between sources)

±15°

±1° to ±45° (1° steps)

 

 

 

Retransfer

Automatic (YES)

Manual (NO)

(return to preferred source after transfer)

 

 

 

 

 

For additional customization of your Epsilon STS™ (e.g. to change the retransfer time delay from the factory setting of 10 seconds), we recommend that you contact our MGE Customer Support (reference page QS-8).

86-504004-00 B03

Operation

3 —15