Installation and User Manual
3.15Epsilon STS™ Customization
Certain parameters can be customized as follows:
1.Press the <Menu> button.
2. Select <Setup>, then <Customization> using the function buttons marked | or | . |
3.Confirm by pressing the function button marked ❚
4.Enter the password (default factory password is “0 0 0”. Select Setup, then Password to change the password).
Figure
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Customization active |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Nominal Voltage | 480V |
|
|
|
|
|
|
| |||
|
| Overvoltage threshold | 10% |
|
|
|
|
|
|
|
|
| |
|
| Undervoltage threshold | 10% |
|
|
|
|
|
|
|
|
| |
|
| Nominal frequency | 60 Hz |
|
|
|
|
|
|
| |||
|
| 5% |
|
| ES |
|
| ||||||
|
| 5% |
|
|
|
| |||||||
|
|
|
|
| C |
|
| ||||||
|
| Phase error tolerance S1/S2 | 15° |
|
|
|
|
|
|
|
|
| |
|
| Retransfer | YES |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Table
Parameter | Factory setting | Customization |
Nominal Voltage (both sources) | As specified by customer | 208,220,240,440,480,575,600V |
|
|
|
Overvoltage threshold | +10% | +5% to +20% (1% steps) |
|
|
|
Undervoltage threshold | ||
|
|
|
Nominal Frequency (both sources) | 60 Hz | 50 or 60 Hz |
|
|
|
+5% | +1 to +10% (0.5% steps) | |
|
|
|
|
|
|
Phase error tolerance (between sources) | ±15° | ±1° to ±45° (1° steps) |
|
|
|
Retransfer | Automatic (YES) | Manual (NO) |
(return to preferred source after transfer) |
|
|
|
|
|
For additional customization of your Epsilon STS™ (e.g. to change the retransfer time delay from the factory setting of 10 seconds), we recommend that you contact our MGE Customer Support (reference page