Epilson STSTM

3.2.1Normal Start Up Procedure

With all of the initial safety check points verified, the Epsilon STS™ system can now be powered. The following procedure should be used after the Epsilon STS™ system has been commissioned (typically by an MGE Field Service Engineer).

1.Ensure that all switches, CB1, 2, 3A, 3B(if installed), 4 and 5 in the STS are OFF (open).

2.Energize both input sources and check for correct voltage, phase rotation and source synchronization. The STS controls will be powered up and the display LCD should turn on. The LED indicators and mimic diagram should also be functioning. The display and buzzer may indicate an alarm since the source isolation switches, CB1 and CB2 are open.

3.If external load circuit breaker(s) are not installed between the STS output and the load, check that the load is ready for power application.

4.Check that Source #1 is the preferred source (factory default setting) – as indicated on the LCD display and the “Preferred Source S1” LED located in the mimic diagram.

5.Close the Source #1 bypass switch, CB4, which connects the output to Source #1, bypassing the static switch section. Output is now energized by Source #1. The bypass switches are interlocked – see note.

NOTE

CB4 and CB5 bypass switches are key-interlocked.

 

The standard 2-interlock system, lock the opposite bypass

 

switch and remove the key (for the optional 4-interlock system,

 

it is also necessary to open the opposite source isolation

 

switch (CB1 or CB2), lock it, remove the key). Using the

 

removed key(s), unlock and close the selected bypass switch.

 

 

6.Apply power to the load by closing the load-circuit beakers (if installed), including PMM power distribution circuit beakers (where applicable).

7.Close the Source #1 (preferred) isolation switch, CB1. The STS will turn on the preferred source SCR Switch 1. Verify on the LED mimic diagram on the front display panel. Also check the operating status on the LCD screen.

8.Close the Source #2 (alternate) isolation switch, CB2. Verify on the LED mimic diagram on the front display panel. Also check the operating status on the LCD screen – no alarms should be displayed.

9.Static switch operation may now be checked by opening the preferred source isolation switch, CB1. The STS will transfer to the alternate source. Verify on the LED mimic diagram on the front display panel. Also check the operating status on the LCD screen.

10.Re-close the preferred source isolation switch, CB1. After the preset retransfer time delay, the STS will retransfer back to the preferred Source #1.

11.Close the STS output isolation switch(es), CB3A (and CB3B if installed). Source #1 power is now supplied through the static switch to the output of the STS.

12.Open (and lock) the Source #1 bypass switch, CB4. The load is now supplied through the static switch. Verify on the LED mimic diagram on the front display panel. Also check the operating status on the LCD screen.

13.The STS is now in the normal operating mode: CB1, CB2, CB3A and CB3B(if installed) - CLOSED. CB4 AND CB5 - OPEN

LCD screen - Normal Operation

LED Mimic diagram - “Source S1 Available”, “Source S2 Available”, “CB1”, “CB2”, “Switch 1”, “CB3”, “Load” and “In Sync” LED's on.

3 —2

Operation

86-504004-00 B03