2.1Cabinet Placement and Environment
The complete STS system may consist of more than one cabinet depending on whether the STS is a
The Epsilon STS™ is intended for use in an environment where control of temperature and humidity is provided. The maximum operating and recommended environmental parameters are listed in Appendix B.
The Epsilon STS™ cabinets generate heat and exhaust air through the top portion of its enclosures. Air intake is through the lower front or bottom of the cabinet. All other auxiliary cabinets are convection cooled. To assist you in planning for your HVAC needs, heat rejection data is provided in Table 2.1 for a worst case scenario (i.e., maximum rated power output).
Table
Data Rate
STS Module | BTU/Hr |
200A 5,600
400A 11,400
600A 16,700
2.2Clearances and FootPrint
As can be seen in the following illustration, the footprint for each cabinet is nominally 30" deep. Additionally, adequate space must be included in the front of each cabinet (approx. 36") to allow the door of the cabinet to be opened for service and maintenance procedures.
Figure
CEILING | CEILING |
|
12" MIN.
12" MIN.
RECOMMENDED FOR
RECOMMENDED FOR
AIR EXHAUST
AIR EXHAUST
AIR INLET |
|
|
(DO NOT BLOCK) | AIR INTAKE | AIR INLET |
| ||
| FILTER WINDOW | (DO NOT BLOCK) |
(DO NOT BLOCK)
FLOOR | FLOOR |
|
2 — 2 | Installation |