Installation and User Manual
1.5System Major Components
Source #1 CB1 | Input isolation molded case switch with magnetic trip for isolating SCR static switch |
| #1 and associated components from source S1. |
Source #2 CB2 | Input isolation molded case switch with magnetic trip for isolating SCR static switch |
| #2 and associated components from source S2. |
Output CB3A | Output isolation molded case switch with magnetic trip for isolating both static switch |
| sections from the load. |
Output CB3B | Optional, redundant output isolation molded case switch with magnetic trip (paral- |
| leled with CB3A) for isolating both static switch sections from the load. |
Source #1 Bypass CB4 | Maintenance bypass molded case switch with magnetic trip for bypassing the static |
| switch section and connecting the load directly to source S1. |
Source #2 Bypass CB5 | Maintenance bypass molded case switch with magnetic trip for bypassing the static |
| switch section and connecting the load directly to source S2. |
Keyed Interlocks | Provided on the two bypass switches to prevent closure of both at the same time. |
| An optional interlocking scheme is available for additional keyed interlocks on the |
| source isolation switches to ensure that, prior to bypassing to a particular source, |
| the STS transfers the load to that source if the load is not already being powered by |
| that source. On closure of a bypass switch, the control logic will also shunt trip |
| opposite bypass and input isolation switches if necessary to prevent |
| tion of the two sources. |
SCR Static Switch Assy. | Three heatsink assemblies containing six pairs of |
| and #2 (each having 3 pairs of SCR's) automatically switch the load to either source |
| S1 or S2. |
Control Electronics | The |
| processing and control sequencing to optimize sensing time. |
Front Display Panel | The LCD screen, pushbuttons and LED mimic diagram make up the display. |
Gate Drive & Acq. PCA | Independent gate drive and acquisition circuits for each sources SCR switch. |
Backfeed Protection Assy | A separate redundant circuit for each source provides backfeed protection to ensure |
| that there is no |
| SCR on the inactive source with the upstream circuit breaker open. |
TVSS Assemblies | Optional Transient Voltage Surge Suppressor on each source input. |
|
|
Control Power Supplies | Three, independent DC control power supply assemblies (fed from each of the two |
| sources and the STS output) provide redundant DC control power. |
CB Control Assembly | A separate circuit supplies DC control power (fed directly from the output terminals) |
| for |
| maintenance bypass mode. |
Output Snubber Assembly | Provides preload under |
Communications Card Cage Relay card providing programmable contacts (6 outputs/2 inputs) and JBUS card for RS232 or RS485 connections. Two slots available for options.
Customer Terminal Block Terminals for connection of remote Emergency Power Off (EPO) and Source Loss Test switch.
Fans (400/600A Models only) Ventilation fans provide
Introduction | 1 — 5 |